Section 6: Programming
104 – 2-Wire Smoke
When this PGM is programmed, the onboard PGM functions as an input instead of an output. 2-wire smoke detectors can be
connected to this input, which means that a zone input does not need to be used.
The PGM is also supervised, and a trouble condition is generated if a 2.2KΩ resistor is not present between the PGM terminal and
Aux+.
The 2-wire smoke detector input creates an instant and latching alarm.
107 - External Siren
This output is normally active and provides up to 1A to charge the external sirens battery. When an alarm occurs on the system, this
PGM triggers and deactivates the voltage to the siren, which causes the siren to sound alarm using power from the backup battery.
Use this output with Grade 3 external battery-operated sirens.
Note:
This PGM type works on PGM 3 only.
109 – Courtesy Pulse
Courtesy pulse causes an output to activate for the entry and exit times, plus 2 minutes. This option is typically used to activate a
courtesy light near the exit door for the duration of the entry/exit times.
111 – Keypad Buzzer Follow
PGM output activates with the keypad buzzer when triggered by the events below. The PGM output remains active for the duration of
the keypad buzzer.
l
24-hour supervisory buzzer zone alarm
l
Auto-arm and no activity arming pre-alert.
l
No activity arm pre-alert
l
Entry delay
l
Audible exit fault
l
Audible exit delay
l
Door chime
This PGM type does not activate for local key presses or trouble beeps.
114 – Ready to Arm
This PGM activates when the system is ready to arm (all non-force armed zones on the system are restored). The PGM output de-
activates when an access code is entered to arm the system and the exit delay begins. This PGM operates as described during walk
test mode (if all zones are restored).
115 – System Armed Status
This output activates when all selected partitions are armed (end of the exit delay) in either Stay or Away modes. The output de-
activates when the system is disarmed.
116 – Away Armed Status
This PGM switches on when the system is armed with stay/away zones activated. If the system is armed with the stay/away zones
always active, then the away output is active.
117 – Stay Armed Status
This PGM output activates if the system is armed with the stay/away zones bypassed.
120 – Away Armed with No Zone Bypasses Status
When assigned to a single partition, this PGM output activates when the system is armed with stay/away and night zones active, and
no zones are bypassed.
If assigned to multiple partitions, all partitions must be armed in away mode with no bypassed zones before the PGM activates. If a
force armable zone is violated at the time of arming, the PGM does not activate. When the zone is restored, the PGM activates.
121-124 – Command Outputs 1-4
Command Outputs 1-4 are user-activated by entering [*] [7] [1-4] at any keypad. When an output is activated, three acknowledgment
beeps are sounded.
PGM outputs of this type can be programmed to follow a pre-defined schedule (programmed in section
). Even if the output follows a schedule it can be manually turned ON, OFF or follow the schedule through [*][7].
To select a schedule for these PGM outputs to follow, see