Section 6: Programming
The internal date and time will be automatically programmed by the primary receiver only.
[225] Cellular Test Transmission Cycle
Default (000000)
This value represents the interval in between test transmissions in minutes. Valid range: 000000 - 999999 minutes. Once the unit has
sent the initial periodic test transmission, all future test transmissions will be offset by the programmed number of minutes. See
sections [026] - [029].
Table 6-9: Cellular Test Transmission Interval
Test Transmission Interval
Daily
Weekly
Monthly
Programmed Minutes
001440
010080
043200
Note:
Minimum value is 000005 minutes. Programming an interval that is less than 5 minutes will disable test transmission.
[226] Network Trouble Delay Timer
Default (015)
This option is used to program the delay, in minutes, for reporting a cellular trouble delay. Valid entries are 000 - 255. When this
section is programmed as 00, Cellular, Ethernet and Supervision troubles are not communicated.
[227] Voice Call Timeout
Default (000) Valid entries are 000 - 255.
[228] Voice Call Back Time
Default (010) Valid entries are 000 - 255.
[229] Voice Call Back Number
Default ( ) 32 digit phone number.
Valide entries:: 0000000000000001 to FFFFFFFFFFFFFFFE
[422] Integration Identification Number
This section will display the unique 12-digit number assigned to this control panel for the identification when integrated with third
party applications.
[423]Session 1 Integration Access Code
Default (12345678123456781234567812345678) Valid Range is 0000000000000000 - FFFFFFFFFFFFFFFF.
This section is a programmable 32-digit number used for initialization with third party applications.
Note:
If integrating with a third party application, this Access Code field must be programmed to a unique number in oder to secure
the connection with 128 bit encryption.
[424] Session 1 SMS Label
Default (11111111)
This section is used to identify the integration session with a third party integrator.
[425] Session 1 Integration Toggle Options 2
The toggle options in this section are used to enable and configure the path used for integration with third party applications.
[1] Integration over USB
Default (OFF)
[2] Integration over Cellular
Default (OFF)
[3] Integration over Ethernet
Default (OFF)
[4]ITv2 Integration Protocol
Default (ON)
[426]Session 1 Integration Toggle Options 3
The toggle options in this section are used to determine the polling and notification behavior used for integration with third party
applications.
[1] UDP Polling
Default (OFF)
[2] TCP Polling
Default (OFF)
[3] Real-time Notification
Default (OFF)
[4] Notification Follows Poll
Default (OFF)
[5] Firewall IP
Default (OFF)
[427] Session 1 Interactive Polling Interval in Seconds
Default (00010) Valid range: 00000-65535
- 149 -