Emergency Stop Switches

 

 

                     

          

 

  

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Standards:

 

IEC 60947-5-5    UL508    EN ISO 13850 

                                                     Case Material 

Stainless Steel 316 or Plastic 

Safety Contact type 

IEC 60947-5-1   Double break Type Zb       

Contact Material 

Silver 

Termination 

Clamp up to 2.5 sq. mm conductors 

Rating 

Utilisation Category :    AC15      

Operational Rating 

AC15  A300    240V. 3A /120V  6A. ac 

Thermal Current  (Ith) 

10A. 

Rated Insulation Voltage (Ui) 

500V. 

Withstand Voltage  (Uimp) 

2500V. 

Short Circuit Overload Protection 

Fuse Externally   10A. (FF) 

Operating Temperature 

-25C  / 80C. 

Enclosure Protection 

IP67 Plastic  or  IP69K Stainless Steel (NEMA 6) 

    

    Optional Explosion Proof Contact Block: 

Classification 

 

Rated Voltage 

Rated Current 

 

 Safety Classification and Reliability Data: 

 Mechanical Reliability B10d 

ISO 13849-1 

EN 62061 

Safety Data  -  Annual Usage  

PFHd 

Proof Test Interval (Life

MTTFd 

 
 
Ex d IIC T6 (-20C Ta 60C) Gb 
Ex tb IIIC T85C (-20C Ta 60C) Db 
250V ac/dc 
2 pole 4A.       4 pole 2.5A. 
 
 
1.5 x 10

6

 operations at 100mA load 

up to PLe depending upon system architecture 
up to SIL3 depending upon system architecture 
8 cycles per hour / 24 hours per day / 365 days  
<1.0 x 10

-7 

 21 years 
214 years 

IMPORTANT NOTE: 

 

Read and understand these instructions before installing, operating, or maintaining this equipment. 

The product is designed to be a component of a customised safety orientated control system. It is the responsibility of each manufacturer to ensure the correct overall functionality of its 
systems and machines. IDEM, its subsidiaries and affiliates, are not in a position to guarantee all of the characteristics of a given system or product not designed by IDEM. 

 

Application: 

Emergency Stop Switches are mounted on machines and sections of plant conveyors that cannot be protected by guards.  
In combination with any dual channel safety monitoring controllers these switches can be used as emergency stop devices and monitored for up to Category 4/PLe to ISO13849-1. 
 

Operation:

 

All Emergency Stop Switches conform to European Standard EN ISO 13850 and IEC 60947-5-5. They have a positive mechanical linkage between the switch contacts and the 
E-Stop Button. The switches are mechanically latched and can then only be returned to the operational condition by a pressing the reset button as required by EN ISO 13850 
and IEC 60947-5-5. 
 

 

Installation Guide: 

1. Installation of all switches must be in accordance with a risk assessment for the individual application and in accordance with local wiring regulations and EN60204-1.  
 Installation must only be carried out by competent personnel and in accordance with these instructions. 

 

2. M4 mounting bolts must be used to fix the switches. Tightening torque for mounting bolts to ensure reliable fixing is 4 Nm. Tightening torque for the lid screws, conduit entry plugs and 
cable glands must be 1.5 Nm to ensure IP seal. Only use the correct size gland for the conduit entry and cable outside diameter. 
 
3. Check operation of all switches and the control circuits by activating the switch (depress the Red Button) and resetting each switch by twisting the Red Button. Ensure each time that 
the switches latch off and require manual resetting. 
 
4. For versions with the Protection Shroud ensure that the padlock size is suitable to prevent re-setting of the button. 
 

Maintenance: 

Every Week:       Check correct operation of the control circuits and latching mechanism. 
                           Inspect for damage to the E Stop button or casing. 
Every 6 Months:  Isolate power and remove cover. Check screw terminal tightness and 
                            check for signs of moisture ingress.  Never attempt to repair any switch.  

 

Operating Instructions     

 

Type ES-P (Plastic) 

Knock –out for 

plastic version 

Type ES-SS 

(Stainless Steel) 

Mirror Polished Finish 

Type ES-SS(P) 

(Stainless Steel) 

With button protection 

shroud with padlock 

holes for lock off during 

maintenance 

Type ESL-SS 

(Stainless Steel) 

Type ESL-SS(P) 

(Stainless Steel) 

With button protection 

shroud with padlock 

holes for lock off during 

maintenance 

Type ESL-SS(L) 

(Stainless Steel) 

With 2-colour LED

 

LED Wiring examples (if fitted): 

Black (or Terminal 2) is 0V (or Neutral for 110V and 230V ac versions). 
When power is applied to the Red wire (or Terminal 1), the LED will illuminate Red. 
When power is applied to the Green wire (or Terminal 3), the LED will illuminate Green. 
 

LED has 2 colours 
Recommended Colour Usage: 

Flashing or Steady Red – Stopped 
LED Steady Green - Run 

 
 

Terminal 2 or Black 

 
 

 
 

            

Terminal 1 or Red 

 

          Terminal 3 or Green

 

  

Wiring circuits for Explosion Proof Versions: 

 1 NC   1 NO 

 

2 NC   2 NO 
 

2 NC 
 

INFORMATION WITH REGARD TO UL508: 

      Type 1 Enclosure 
      Contact Blocks A300    230V/3A   120V/6A 
      Wire range: 16AWG – 12AWG Copper   Torque 7lb/in (0.8Nm) 
      LED powered by LVLC or Class 2 only. 

Type ESL-SS(LP) 

(Stainless Steel) 

With 2-colour LED and 

button protection 

shroud with padlock 

holes for lock off during 

maintenance 