Section 2: Installation
Mounting the enclosure
This section provides basic instructions for wall-mounting the available PowerSeries Pro enclosures. Mount in a dry location, near an
unswitched AC power source and Ethernet and phone connections.
Note:
Complete all wiring before applying AC or connecting the battery.
Note:
The weight of the enclosure and contents cannot be supported by drywall only. Use mounting hardware sufficient to support up
to three times the panel weight, including equipment, cables, conduit and hardware (approximately 210 lbs/ 95 kg). Select hardware
suitable for the mounting surface. Recommended minimum screw size: M4 (#8) x 4, 25.4 mm (1 inch) long, pan head.
To mount the enclosure, complete the following steps:
1. Position the enclosure in the mounting location and mark the two top screw holes and the tamper bracket hole.
2. Remove the enclosure, then install the two top screws part way and an anchor for the tamper bracket, if necessary. Do not mount
the tamper bracket directly into drywall.
3. Hang the enclosure on the installed screws then mark the two bottom mounting holes.
4. Remove the enclosure from the wall and install the components in the following order:
l
Plastic standoffs for alarm controller and optional modules
l
Tamper switch and bracket
l
Power supply, including GND connection for HSC3010C, HSC3010CR, and HSC3030CAR enclosures (see diagram).
Note:
The ground screw mounts from the back of the cabinet.
5. Hang the enclosure on the top two screws again then fasten the tamper bracket to the wall.
6. Install the two bottom screws, ensure that all four screws are securely tightened.
7. Install the alarm controller. For models HSC3010C, HSC3010CR, HSC3030CAR and HSC3020C enclosures, use the supplied
metal standoff and screw in bottom-right mounting hole as indicated in Figure 2-1.
8. Install optional modules and wire according to the instructions provided with the module.
9. Wire the tamper switch into any available zone. Configure the tamper for normally closed (NC) supervision. Zone must be
programmed for 24-hour latching or non-latching tamper.
10. Install the batteries only after the enclosure has been permanently secured to the wall.
Note:
For NFA2P certified systems, when using the cellular communicator 3G9080-EU, install tamper cover part number 09000996.
See
Figure 2-1: Installing the tamper cover
- 12 -