Section 2: Installation
Terminal descriptions
The following terminals are available on the PowerSeries Pro alarm controller.
Table 2-1: Terminal descriptions
Terminal
Description
BAT+, BAT- Battery terminals. Use to provide backup power during a power outage and additional current when system demands
exceed the power output of power adapter. Do not connect the battery until all other wiring is complete.
DC +, DC - The HS65WPS power adapter supplies 18 VDC power input to the alarm controller.
Note:
CE/EN certified applications use power adapter HS65WPS. UL/ULC listed applications use power adapter
HS65WPSNA. ULC Commercial Fire Listed applications and ULC Commercial Burg Security Level 4 applications use
power adapter HS65WPSNA.
AUX+,
AUX-
Auxiliary terminals. Use to connect power detectors, relays, LEDs, etc. (2 A max). Connect the positive side of device to
one of the three AUX+ terminals and the negative side to AUX- or COM.
BELL+,
BELL-
Bell/Siren power (700 mA continous, 2A max short term). Connect the positive side of any alarm warning device to
BELL+, the negative side to BELL-.
Note:
For EN50131 and UL/ULC listed applications, use maximum 700 mA load on the BELL output.
RED, BLK,
YEL, GRN
Corbus terminals. Use to provide power and communication between the alarm controller and connected modules.
Each module has four Corbus terminals that must be connected to the Corbus.
PGM1 to
PGM4
Programmable output terminals. Use to activate devices such as LEDs, relays, buzzers, etc. (PGM1, PGM4: 100 mA;
PGM2: 300 mA or can be configured for use as a 2-wire smoke detector interface, max loop current 100 mA; PGM3:
300 mA (negative trigger) or 1 A (positive trigger)
Z1 to Z8
COM
Zone input terminals. Each zone should have one detection device; however, multiple detection devices can be wired
to the same zone.
EGND
Earth ground connection
ETHERNET Ethernet port
TIP, RING,
T-1, R-1
Telephone line terminals
Wire routing for power & non-power limited
Wire entry for power limited wiring must be separated by a different entry access from non-power limited wiring.
Corbus wiring
The RED and BLK Corbus terminals are used to provide power while YEL and GRN are used for data communications. The 4 Corbus
terminals of the alarm controller must be connected to the 4 Corbus terminals or wires of each module. The following conditions
apply:
l
Corbus should be run with 18 to 22 AWG quad, two pair twisted preferred.
l
The modules can be home run to the panel, connected in series or can be T-tapped.
l
Do not use shielded wire for Corbus wiring.
Note:
Any module can be connected anywhere along the Corbus. Separate wire runs for keypads, zone expanders etc. are not
necessary.
Note:
No module can be more than 1000 ft / 305 m (in wire length) from the panel.
Do not use shielded wire for Corbus wiring.
Figure 2-21: Corbus wiring
- 33 -