Appendix 5: Regulatory approvals
l
ULC-S559-13 Equipment for Fire Signal Receiving Centers and Systems
l
ULC-S545-02 Residential Fire Warning System Control Units
The subscriber control unit shall provide for the connection of protective wiring, conductors, and attachments in accordance with the
Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681.
This product has also been tested and found in compliance with the ANSI/SIA CP-01-2014 Control Panel Standard – Features for
False Alarm Reduction.
This product is UL/ULC listed under the following categories:
l
AMCX/AMCXC Central Stations Alarm Units
l
AOTX Local Alarm Units
l
APAW Police-station-connected Alarm Units
l
DAYRC Central Station Fire Alarm System Units
l
UTOU/UTOUC Control Units and Accessories, Household System Type
l
NBSX/NBSXC Household Burglar Alarm System Units
l
AMTB Control Panels, SIA False Alarm Reduction
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified in
accordance with SIA-CP-01 Standard) as proof of compliance with the above mentioned standards. For further information on this
product’s listings please also refer to the official listing guides published at the UL web site (www.ul.com) under Online Directions
Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations, refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.
l
Control Unit must be enclosed in model HSC3010C or HSC3020C enclosure.
l
Power supply model SOY-1800360NA (HS65WPSNA) must be employed.
l
24 h standby power must be provided for fire applications and 4h for burglary only applications (AC trouble must be
transmitted to SRC).
l
One DSC Model RM-1 or RM2 end-of-line supervision relay module must be used.
l
Priority of signals needs to be set Fire, CO/ Medical, Burg, Panic, AUX (Flood).
l
All burglary-type zones shall be configured with SEOL or DEOL configuration. Use model EOLR-2
l
(refer to section [002], bit 10 or 11 shall be ON)
l
Use at least one PG9926/ PG9916/ PG9936 Smoke Detector for Fire Installations (section [001], fire zone shall be
programmed as type 025)
l
The entry delay shall not exceed 45 seconds (see section [005])
l
The exit delay shall not exceed 60 seconds (refer to section [005])
l
The minimum Bell Time-out is 4 minutes (refer to section [005])
Note:
Connect Bell output to a UL/ULC Listed audible device (e.g., UL File S8534, model TS-443S-6), rated to operate over the
range of 10.8 to 12.5 VDC and 85dBA minimum. Wireless sirens PG9901 and PG9911 may also be used as audible devices.
Note:
For ULC Residential Fire installations, minimum bell time-out is 5 min. For UL Home Health Care installations, minimum bell
time-out is 5 min. For UL Commercial Burglary installations, minimum bell time-out is 15 min.
l
Temporal Three Fire Signal shall be enabled (section [013], opt.8 ON)
l
Arm/Disarm Bell Squawk shall be enabled when using wireless key PG4939/PG4929/PG4949 (section [014], option 1 shall
be ON)
l
A code shall be required for bypassing (section [023], option 4 shall be ON)
l
Trouble beeps shall be enabled (section [022], option 7 shall be ON)
l
AC trouble indication LED shall be enabled (Keypad Programming, section [022], options 5 and 6 shall be ON)
l
DACT Communicator shall be enabled for Supervising Station Monitoring (section [380], option 1 shall be ON)
Note:
The DACT communicator for this product has no line security.
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be ON)
This product is programmed to perform 5 attempts for communication of an event to the supervising station. If unsuccessful, a Fail To
Communicate (FTC) trouble is generated.
Test transmission cycle shall be set (refer to section [351]) for monthly transmission for UL residential burglary applications and to 7
days for UL residential fire applications.
Note:
For ULC Residential/Commercial installations set for daily test transmission.
l
For UL Residential Fire installations, [*][2] requires code shall be enabled (Section [023] option 5 ON) and latching troubles
shall be enabled (Section [019] option 2 ON)
l
If a repeater is needed, two repeaters model PG9920 shall be used to ensure proper signal routing.
l
Wireless Supervision window shall be set to 4 hours for Fire Installations (Wireless Programming, section [804]>[802] shall be
programmed with the value 16)