Section 6: Programming
5/6 – Auxiliary Power Supply Trouble/Restore
This reporting code is transmitted when an auxiliary voltage supply trouble occurs or is restored. This reporting code is sent to the
System Maintenance call direction group.
7/8 – Overcurrent Trouble/Restore
This reporting code is transmitted when an overcurrent trouble occurs or is restored. Current threshold is 2 amps.
[305] Panel Events 5
3/4 – PGM 2 2-Wire Trouble/Restore
This reporting code is transmitted when a trouble condition on PGM 2, configured as two-wire smoke, occurs or is restored. This
reporting code is sent to the System Maintenance call direction group.
[311] Maintenance Events 1
1/2 – RF Jam Trouble/Restore
Sent when RF jam troubles occur/are restored. The following events cause RF jam troubles:
l
Wireless repeater jamming
l
RF jam
3/4 – Fire Trouble/Restore
Sent when a low sensitivity, tamper or internal fault condition/restore is detected on a wireless smoke detector or supervisory fault
with a hardwired smoke detector.
5 – Cold Start
Sent when power is restored to the alarm system after total power failure. The code is sent after 2 minutes to allow the alarm
controller to stabilize.
6 – Delinquency
When the Delinquency option is off (
), this code is transmitted if the alarm system has not been armed for the number of
days programmed in the Delinquency Transmission Delay (
).
When the Delinquency option is on, this code is transmitted when no zone activity has been detected on the system for the number of
hours programmed in Delinquency Transmission Delay.
7 – Self Test Trouble
Sent when a self test trouble occurs for an outdoor PIR.
8 – Self Test Trouble Restore
Sent when a self test trouble has been restored for an outdoor PIR.
[312] Maintenance Events 2
1/2 – Installer Lead In/ Lead Out
The Installer Lead In and Lead Out reporting codes are sent when the alarm system enters and exits Installer Programming
respectively.
3/4 – DLS Lead In/Lead Out
The DLS Lead In reporting code is sent:
l
after DLS communication has been successfully established, but before the alarm system calls back the downloading
computer. This code is only transmitted when call back is enabled.
l
on user-initiated call-up.
The DLS Lead Out reporting code is sent when a DLS session is successfully ended.
Note:
If DLS is terminated by an alarm, the DLS Lead Out reporting code is not transmitted.
5/6 – SA Lead In/Lead Out
The SA Lead In reporting code is sent:
l
after SA communication has been successfully established, but before the alarm system calls back the downloading
computer. This code is only transmitted when call back is enabled.
l
on user-initiated call-up.
The SA Lead Out reporting code is sent when an SA session is successfully ended. The SA Lead Out reporting code is still sent if the
session is terminated by an alarm.
7 – Event Buffer 75% Full
Sent when the event buffer reaches a threshold of 75% without being uploaded.