Appendix 5: Regulatory approvals
SIA Feature Programming
Section
Comments
Range/Default Requirement
Cross Zoning
[042]>Selection 3, option 002
Enables cross zoning for entire system. Zones can be
enabled for cross zoning via zone attribute option 8 in
sections [002][101] - [248].
Programming
required
Default:
Disabled
Required
Burglary Verification Timer
[005]>[000], option 3
Access to the programmable Cross Zone timer.
Range: 000-
255 sec.
Default: 60
seconds
Allowed
Swinger Shutdown for Alarms
[377]>[001], option 1
Access to the swinger shutdown limit for zone alarms.
For all non-fire zones, shut down at 1 to 6 trips.
Default: 2 trips
Required
(programmable)
Swinger Shutdown Enable
[002]>[001] - [248], option 6 ON
Access to swinger shutdown, transmission delay and cross
zone attributes. Zone attribute option 6 (Swinger Shutdown
enabled) is ON.
Non-police
response
zones
Default:
Enabled
Allowed
24-Hr. Auto-verified Fire
[001]>[001]-[248], Zone type 025
ON
Access to 24-Hr. Auto-verified Fire.
Activates if Not restored within the specified time.
Must choose
zone type for
application
Required
Call Waiting Cancel
[382], option 4 OFF
Access to the dialing sequence used to disable call waiting.
Call waiting string can be programmed in [304].
Depends on
user phone line
Default:
Disabled
Required
System Test:
[*][6] Master Code, option 04
The system activates all keypad sounders, bells or sirens for 2
seconds and all keypad lights turn on. Refer to user manual.
Walk Test Mode:
[*][8][Installer code][901]
This mode is used to test each zone on the system for proper
functionality.
Walk Test Communications
[382], option 2
Enables communication of zone alarms while walk test is
active.
Default:
Disabled
Walk Test Start/ End Reporting
Codes
[308][401], options 1 and 2
Access to the reporting codes for walk test start and end times.
Duress Code
Duress codes function the same as user access codes, except they transmit a duress reporting
code when used to perform any function on the system. Duress codes cannot be used to access
[*][5], [*][6] or [*][8] menus.
Duress codes are created by the master user or supervisor users
5.5 European EN50131 Compliance Statement
This Product (HS3032/HS3128/HS3248) meets the requirements of Grade 3, Class II equipment as per EN50131-1:2006 + A1:2009
+ A2:2017 Standards. The Model HS3032, HS3128, HS3248 Control Panel has been certified by Telefication according to EN50131-
1: 2006 +A1:2009+A2:2017, EN50131-3:2009 Type B, EN50131-6:2017 Type A, EN50131-10, EN50136-2:2013 ATS SP3 (dialer),
SP4 (Ethernet), DP2 (dialer and Ethernet), DP3 (Ethernet and plug-in cellular) when installed in enclosure models HSC3020C or
HSC3020CP.
Note:
Models HS3032P, HS3128P, HS3248P consisting of control panel board assembly HS3032, HS3128, HS3248 with
HSM2HOST8 Wireless Transceiver mounted in the HSC3020CP plastic enclosure meets the requirements of Grade 2, Class II
equipment as per EN50131-1:2006 + A1:2009 + A2:2017 Standards. The model HS3032P, HS3128P, HS3248P has been certified
by Telefication according to EN50131-1: 2006 +A1:2009+A2:2017, EN50131-3:2009 Type B, EN50131-6:2017 Type A, EN50131-10,