Section 6: Programming
[001]-[324] PGM Partition Assignment
This option enables the installer to assign each PGM output to a partition. To assign a PGM to a partition, first select the PGM output
(PGM 001-324), then select the partition (1-32).
Note:
This field is only supported by PGM types that have multiple partition capabilities (e.g., command outputs, away arming). It does
not affect system outputs (e.g., ground start pulse).
[008] PGM Timer Programming
[000] PGM Minutes/Seconds
This option determines if the timer is in minutes or seconds.
[001]-[324] PGM Timer
This timer programs the duration (in seconds or minutes) that PGMs 1-324 activate if programmed to follow the PGM Timer.
Select option 001-324 for PGM 1-324.
This option does not affect outputs programmed as Sensor Reset.
[009] PGM Types
The output types described in this section can be assigned to alarm controller and output expander module PGMs. Each alarm
controller supports up to 4 PGMs and can be expanded using HSM2208 output expander, HSM3204CX and HSM2204 High-Current
output modules. PGM attributes are defined in section
"[010] PGM Attributes" on page 101
[001]-[324] Select PGM
100 – Null PGM
This option deactivates the PGM output
101 – Burglary and Fire Bell Follower
This PGM output follows:
l
Fire pre-alerts
l
Temporal three fire signal (if enabled)
l
All audible burglary and fire alarms by partition
l
Bell cut-off time
l
Bell squawk conditions
l
Audible exit fault
This output activates when the alarm output is active and turns off when the alarm output is silenced. The siren pattern matches the
programmed cadence for the zone that went into alarm. Cadence priority is as follows:
l
fire alarm cadence
l
CO alarm cadence
l
other alarm cadences
The main siren still activates for all alarms.
102 – Delayed Fire and Burglary
This output type operates the same as the Burglary and Fire Bell Follower (PGM type 01), but does not activate until the transmission
delay time expires.
When a zone with transmission delay enabled is tripped, the Bell, Regular Fire and Burglary PGMs activate. At the end of the
transmission delay, the delayed Fire and Burglary output activates.
This PGM is usually used to control outdoor sirens. If a false alarm occurs, the user has time to disarm the system before the external
sirens activate.
Note:
If a zone alarm occurs but does not follow transmission delay, this PGM activates immediately, even if transmission delay is
active for a different zone alarm.
This output activates for audible exit fault and does not interfere with the operation of any other programmable output.
103 – Sensor Reset [*][7][2]
This output is normally active and deactivates for 5 seconds when a [*][7][2] fire reset command is entered or when an auto verified
fire alarm is detected. This option is used to reset power for latching smoke detectors. The keypad buzzer does not sound for the 5-
second period.
See "Smoke detector wiring" on page 49
for instructions on wiring smoke detectors.
- 96 -