Case Temperature Reference Metrology
Thermal and Mechanical Design Guidelines
79
Figure 31. Omega Thermocouple
D.3
Thermal Calibration and Controls
It is recommended that full and routine calibration of temperature measurement
equipment be performed before attempting to perform case temperature
measurements. Intel recommends checking the meter probe set against known
standards. This should be done at 0 ºC (using ice bath or other stable temperature
source) and at an elevated temperature, around 80 ºC (using an appropriate
temperature source).
Wire gauge and length also should be considered as some less expensive
measurement systems are heavily impacted by impedance. There are numerous
resources available throughout the industry to assist with implementation of proper
controls for thermal measurements.
NOTES:
1.
It is recommended to follow company standard procedures and wear safety
items like glasses for cutting the IHS and gloves for chemical handling.
2.
Ask your Intel field sales representative if you need assistance to groove
and/or install a thermocouple according to the reference process.
D.4
IHS Groove
Cut a groove in the package IHS according to the drawing given in Figure 32.
Summary of Contents for QX68000 Core 2 Extreme
Page 30: ...LGA775 Socket Heatsink Loading 30 Thermal and Mechanical Design Guidelines...
Page 74: ...Heatsink Clip Load Metrology 74 Thermal and Mechanical Design Guidelines...
Page 76: ...Thermal Interface Management 76 Thermal and Mechanical Design Guidelines...
Page 96: ...Case Temperature Reference Metrology 96 Thermal and Mechanical Design Guidelines...
Page 108: ...Legacy Fan Speed Control 108 Thermal and Mechanical Design Guidelines...
Page 112: ...BTX System Thermal Considerations 112 Thermal and Mechanical Design Guidelines...