Legacy Fan Speed Control
106
Thermal and Mechanical Design Guidelines
Table 13. ATX FSC Settings
Parameter Classification Processor
Thermal Sensor
PWM Output
Notes
T
HIGH
Required
T
CONTROL
3
T
LOW
Required
T
CONTROL
– 10 °C
3
Minimum PWM Duty
Cycle
Required 20%
PWM Frequency
Required
21-28 kHz
1
Spin-up time
Suggested
250 - ~500 ms
2, 4
T
AVERAGING
Suggested
35
sec
4
When T
SENSOR
< T
LOW
Suggested Minimum
PWM%
All Fans ON
Suggested
T
CONTROL
+ 3 °C
Hysteresis Suggested
2
°C
NOTES:
1.
A PWM frequency of 25 kHz is the design target for the reference and for the Intel
®
Boxed Processor and the reference design..
2.
Use the lowest time available in this range for the device selected.
3.
To ensure compliance with the thermal specification, thermal profile and usage of the
T
SENSOR
for fan speed control these setting should not be user configurable.
4.
If this function is present on the device it must be enabled
Table 14. BTX Fan Speed Control Settings
Parameter Classification Processor
Thermal
Sensor
System
Ambient
Sensor
PWM
Output
Notes
T
HIGH
Required
T
CONTROL
54
°C 3,5
T
LOW
Required
T
CONTROL
– 7 °C
47 °C
3,5
Minimum PWM
Duty Cycle
Required
PWM
1
(TMA) –20%
PWM Frequency Required
21-28
kHz 1
Spin Up Time
Suggested
250 –
~ 500 ms
2, 7
T
AVERAGING
Suggested
4.0 sec
4.0 sec
3,
7
When T
SENSOR
<
T
LOW
Suggested Minimum
PWM%
Minimum
PWM%
All Fans On
Suggested
T
CONTROL
+ 3 °C
65 °C
Hysteresis
Suggested
2 °C
4 °C
NOTES:
1.
A PWM frequency of 25 kHz is the design target for the reference and for the Intel
®
Boxed Processor and the reference design.
2.
Use the lowest time available in this range for the device selected
3.
T
AVERAGING
= represents the amount of delay time before responding to the temperature
change, defined in fan speed control device (sometimes called ramp range control or
Summary of Contents for QX68000 Core 2 Extreme
Page 30: ...LGA775 Socket Heatsink Loading 30 Thermal and Mechanical Design Guidelines...
Page 74: ...Heatsink Clip Load Metrology 74 Thermal and Mechanical Design Guidelines...
Page 76: ...Thermal Interface Management 76 Thermal and Mechanical Design Guidelines...
Page 96: ...Case Temperature Reference Metrology 96 Thermal and Mechanical Design Guidelines...
Page 108: ...Legacy Fan Speed Control 108 Thermal and Mechanical Design Guidelines...
Page 112: ...BTX System Thermal Considerations 112 Thermal and Mechanical Design Guidelines...