ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
69
5.3.16
Module 14 – analogue input master 1
10658
Data content
10654
Analogue input data of the analogue slaves to AS-i master 1
With module 14 the data of the analogue input slaves on AS-i master 1 with the following AS-i slave
addresses can be directly read:
1...31 (setting = 4 channels per slave),
1...31 (setting = 1 channel per slave).
Change of the setting:
chapter
Setting "Number of channels per analogue slave"
(
→
page
)
Shall an analogue input channel outside the above-mentioned ranges be read?
►
Use the following module to read these data:
Module 9 – analogue multiplexed input
(
→
)
Direction of data
10590
C
F
Data from the controller to the fieldbus interface
Module settings
10659
Value range = 0...31
- 4 words of data for 4 channels per slave
- 2 words of data for 1 channel per slave
0
module is deactivated
1...31
module is activated (details
data interpretation)