ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
38
No.
Module
Direction of
data
Possible settings
Information about the setting values
1
digital input master 1(A)
C
F
2
digital output master 1(A)
C
F
3
digital input master 2(A)
C
F
4
digital output master 2(A)
C
F
5
digital input master 1B
C
F
6
digital output master 1B
C
F
7
digital input master 2B
C
F
8
digital output master 2B
C
F
0…16
0
deactivated
number of bytes
9
analogue multiplexed input
C
F
10
analogue multiplexed output
C
F
11
fieldbus data command channel
C
F
0 / 1
0
1
deactivated
activated
12
fieldbus data PLC input
C
F
13
fieldbus data PLC output
C
F
0…128
0
deactivated
number of bytes
14
analogue input master 1
C
F
0…31
0
deactivated
4 words of analogue data
respectively
15
analogue output master 1
C
F
0…17
0
17
deactivated
4 words of analogue data
respectively
31x 4 words of analogue data
16
analogue input master 2
C
F
0…31
0
deactivated
4 words of analogue data
respectively
17
analogue output master 2
C
F
0…17
0
17
deactivated
4 words of analogue data
respectively
31x 4 words of analogue data
18
fieldbus data diagnosis
C
F
0 / 1 / 2
0
1
2
deactivated
activated for master 1
activated for master 1 + 2
19
host command channel
C
F
0 / 1 / 2
0
1
2
deactivated
activated (5 words)
activated (18 words)
C
F
data from controllerE to fieldbus interface (controllerE output data)
C
F
data from fieldbus interface to controllerE (controllerE input data)
C
F
bidirectional data (controllerE output data as well as controllerE input data)