Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
68
Example for module 13
10656
Task:
Process data with a total length of 50 bytes are to be transmitted by the controller to a higher-
level PLC. To which value must module 13 be set?
Solution:
The data length is 50 bytes.
Thus, module 13 must be set to a length of at least 50 bytes in order to transmit all data.