ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
The fieldbus command channel (module 11)
Module 11, command 16dec (10hex) – change current slave parameters
119
6.15.3
Example: change slave parameter of slave 7 on AS-i
master 1 to the value [F]
4791
Request from fieldbus master to device
Word no.
Value [hex.]
Meaning
1 4710
(slave no.
7
)
+ (master no.
1 * 64
)
+ (32, if B slave)
= 71
dec
=
47
hex
10 = command 16
2 0000
not
used
Response from device to fieldbus master
Word no.
Value [hex.]
Meaning
1 4710
copy of the request
command processed, no error occurred
2
000F
0F = parameter feedback value (can be different from the preset value)