Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Set-up
Set the parameters of the device
226
Analogue
multiplex output
1
OK
108
ESC
Step 15:
> Indicates that the fieldbus module 10 (analogue multiplex output) is
activated.
►
Press [ ] / [ ] to set the requested number of bytes.
►
Press [OK] to save the settings and scroll to the next display.
OR:
►
Use [ESC] to return to screen 87 [Fieldbus IP Address]
Fieldbus Data
Command channel
1
OK
109
ESC
Step 16:
> Indicates that the fieldbus module 11 (fieldbus data command
channel) is activated.
►
Press [ ] / [ ] to set the requested number of bytes.
►
Press [OK] to save the settings and scroll to the next display.
OR:
►
Use [ESC] to return to screen 87 [Fieldbus IP Address]
10858
Fieldbus Data
PLC input
8
OK
110
ESC
Step 17:
> Indicates that the fieldbus module 12 (fieldbus data PLC input) with a
length of 8 bytes is activated.
►
Press [ ] / [ ] to set the requested number of bytes.
►
Press [OK] to save the settings and scroll to the next display.
OR:
►
Use [ESC] to return to screen 87 [Fieldbus IP Address]
Fieldbus Data
PLC output
10
OK
111
ESC
Step 18:
> Indicates that the fieldbus module 13 (fieldbus data PLC output) with
a length of 8 bytes is activated.
►
Press [ ] / [ ] to set the requested number of bytes.
►
Press [OK] to save the settings and scroll to the next display.
OR:
►
Use [ESC] to return to screen 87 [Fieldbus IP Address]
Analogue input
Master 1
10
OK
112
ESC
Step 19:
> Indicates that the fieldbus module 14 (analogue input master 1) with a
length of 10 x 4 words is activated.
►
Press [ ] / [ ] to set the requested number of bytes.
►
Press [OK] to save the settings and scroll to the next display.
OR:
►
Use [ESC] to return to screen 87 [Fieldbus IP Address]