Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
42
The data is stored as double words:
DW
double word
Bit
DW
3
1
3
0
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
9
1
8
1
7
1
6
1
5
1
4
1
3
1
2
1
1
1
0
0
9
0
8
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
Word n+1
Word n
Bit
word
1
5
1
4
1
3
1
2
1
1
1
0
0
9
0
8
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
1
5
1
4
1
3
1
2
1
1
1
0
0
9
0
8
0
7
0
6
0
5
0
4
0
3
0
2
0
1
0
0
1
Byte 4
Byte 3
Byte 2
Byte 1
2
Byte 8
Byte 7
Byte 6
Byte 5
3
Byte 12
Byte 11
Byte 10
Byte 9
4
Byte 16
Byte 15
Byte 14
Byte 13
Bit
byte
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Examples for module 2
10597
Task 1:
The digital output signals of the AS-i slaves 1 and 2 are to be transmitted. To which value must
module 2 be set?
Solution:
The highest used AS-i slave address is 2. According to the table, the data of the AS-i slave 2 are
stored in byte 2 of the module. Therefore, module 2 must be at least set to the value 2.
Task 2:
The digital output signals of the AS-i slaves 5, 17 and 30 are to be transmitted. To which value
must module 2 be set?
Solution:
The highest used AS-i slave address is 30. According to the table, the data of the AS-i slave 30
are stored in byte 16 of the module. Therefore, module 2 must be set to the value 16.