ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
41
5.3.2
Module 2 – digital output master 1(A)
10556
Data content
10594
Binary output data of the digital single or A slaves of AS-i master 1
Direction of data
10595
C
F
Data from the fieldbus interface to the controllerE
Module settings
10591
Value range: 0…16 [bytes]
0
module is deactivated
1...16
module is activated (details
data interpretation)
Data interpretation
10596
In each transmitted byte, the digital signals of 2 AS-i slaves can be transmitted. The position of the
data in this memory range depends on the AS-i address of the corresponding slave. Therefore the
value to be set is based on the highest AS-i slave address of the used digital output slaves and not on
the number of used slaves.
The following table shows the allocation of AS-i slave addresses to the module settings.
The data range of AS-i slave address 0 is not used.
Setting value
[byte]
AS-i slave addresses
Setting value
[byte]
AS-i slave addresses
1
––
1
9
16 17
2
2 3
10
18 19
3
4 5
11
20 21
4
6 7
12
22 23
5
8 9
13
24 25
6
10 11
14
26 27
7
12 13
15
28 29
8
14 15
16
30 31
Bit
7
6
5
4
3
2
1
0
Bit
7
6
5
4
3
2
1
0