ifm
Supplementary device manual DeviceNet interface in the AS-i ControllerE (AC1318, AC1324), Target from 15
2012-02-29
Function
The fieldbus modules
53
5.3.11
Module 9 – analogue multiplexed input
10579
Data content
10625
Analogue input data of the slaves of the AS-i masters 1 + 2
The data of analogue input slaves with the following AS-i slave addresses can be directly read via the
modules 14 and 16:
1...31 (setting = 4 channels per slave),
1...31 (setting = 1 channel per slave).
Change of the setting:
chapter
Setting "Number of channels per analogue slave"
(
→
page
)
So, module 9 only has to be used if the data cannot directly be read via the modules 14 or 16.
chapter
Module 14 – analogue input master 1
(
→
page
)
chapter
Module 16 – analogue input master 2
(
→
page
)
Direction of data
10626
C
F
Bidirectional (2 words = 4 bytes in both directions)
Module settings
10627
Value range = 0 / 1
0
module is deactivated
1
module is activated (details
data interpretation)
Data interpretation
10628
Using module 9, analogue input data of an AS-i slave with any AS-i address can be retrieved.
The information which channel of which AS-i slave on which master is to be read must be given to the
controller via the fieldbus interface. The controller replies to such a request with a copy of the request
data and the corresponding analogue value. As a result, only one specific analogue value can be
transmitted at a time by module 9. This process is called multiplexing.