Table 25. A00-FF0 through A24-xxx SRNs (continued)
SRN
Description
FRU/action
A13-16x
A non-critical error has been detected,
an I/O expansion unit not in an
operating state.
1.
Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 88.
2.
If no entry is found, replace the system-board
and chassis assembly.
A13-50x
Recoverable errors on resource indicate
a trend toward an unrecoverable error.
However, the resource could not be
deconfigured and is still in use. The
system is operating with the potential
for an unrecoverable error.
1.
If repair is not immediately available, reboot
and the resource will be deconfigured;
operations can continue in a degraded mode.
2.
Check the BladeCenter management-module
event log for an entry around this time. If no
entry is found, replace the system-board and
chassis assembly.
A15-01x
Sensor indicates a fan is turning too
slowly.
1.
Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 88.
2.
If no entry is found, replace the system-board
and chassis assembly.
A15-03x
Sensor indicates a voltage outside
normal range.
1.
Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 88.
2.
If no entry is found, replace the system-board
and chassis assembly.
A15-05x
Sensor indicates an abnormally high
internal temperature.
1.
Make sure that:
a.
The room ambient temperature is within
the system operating environment.
b.
There is unrestricted air flow around the
system.
c.
All system covers are closed.
d.
There are no fan failures
2.
Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 88.
3.
If no entry is found, replace the system-board
and chassis assembly.
A15-07x
Sensor indicates a power supply has
failed.
1.
Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 88.
2.
If no entry is found, replace the system-board
and chassis assembly.
A15-11x
Sensor detected a redundant fan failure.
1.
Check the BladeCenter management-module
event log; if an error was recorded by the
system, see “POST progress codes
(checkpoints)” on page 88.
2.
If no entry is found, replace the system-board
and chassis assembly.
174
JS12 Type 7998: Problem Determination and Service Guide
Summary of Contents for BladeCenter JS12
Page 1: ...BladeCenter JS12 Type 7998 Problem Determination and Service Guide...
Page 2: ......
Page 3: ...BladeCenter JS12 Type 7998 Problem Determination and Service Guide...
Page 14: ...xii JS12 Type 7998 Problem Determination and Service Guide...
Page 248: ...234 JS12 Type 7998 Problem Determination and Service Guide...
Page 252: ...238 JS12 Type 7998 Problem Determination and Service Guide...
Page 290: ...276 JS12 Type 7998 Problem Determination and Service Guide...
Page 298: ...284 JS12 Type 7998 Problem Determination and Service Guide...
Page 302: ...288 JS12 Type 7998 Problem Determination and Service Guide...
Page 312: ...298 JS12 Type 7998 Problem Determination and Service Guide...
Page 317: ......
Page 318: ...Part Number 60Y1568 Printed in USA 1P P N 60Y1568...