Supported platforms for trunking
22
Trunks operate best when the cable length of each trunked link is roughly equal to the length of the
others in the trunk. For optimal performance, no more than 30 meters
difference is recommended.
Trunks are compatible with both short-wavelength (SWL) and long-wavelength (LWL) fiber-optic
cables and transceivers.
Trunking is performed according to the Quality of Service (QoS) configuration on the master and the
slave ports. That is, in a given trunk group, if there are some ports with QoS enabled and some with
QoS disabled, they form two different trunks, one with QoS enabled and the other with QoS
disabled. For more information on QoS, refer to
“QoS zones”
on page 525.
High Availability support for trunking
Trunking is a High Availability (HA) supported feature. The HA protocol for trunking is as follows:
•
If trunking is disabled prior to the HA failover, it remains disabled after the HA failover.
•
If trunking is enabled prior to the HA failover, it remains enabled after the HA failover.
Supported platforms for trunking
Trunking is supported on the FC ports of all Brocade platforms and blades supported in Fabric OS
v7.0.0 and later.
EX_Port trunking is supported only on those platforms that support EX_Ports. See
“Supported
platforms for FC-FC routing”
on page 570 for more information.
Requirements for trunk groups
The following requirements apply to all types of trunking:
•
The Trunking license must be installed on every switch that participates in trunking.
•
All of the ports in a trunk group must belong to the same port group.
•
All of the ports in a trunk group must meet the following conditions:
-
They must be running at the same speed.
-
They must be configured for the same distance.
-
They must have the same encryption, compression, QoS, and FEC settings.
•
Trunk groups must be between Brocade switches (or Brocade adapters, in the case of F_Port
trunking). Brocade trunking is proprietary and is not supported on M-EOS or third-party switches.
•
There must be a direct connection between participating switches.
•
Trunking cannot be done if ports are in ISL R_RDY mode. (You can disable this mode by using
the portCfgIslMode command.)
•
Trunking is supported only on FC ports. Virtual FC ports (VE_ or VEX_Ports) do not support
trunking.
Summary of Contents for Fabric OS 7.1.0
Page 1: ...53 1002745 02 25 March 2013 Fabric OS Administrator s Guide Supporting Fabric OS 7 1 0 ...
Page 24: ...24 Fabric OS Administrator s Guide 53 1002745 02 ...
Page 28: ...28 Fabric OS Administrator s Guide 53 1002745 02 ...
Page 32: ...32 Fabric OS Administrator s Guide 53 1002745 02 ...
Page 42: ...42 Fabric OS Administrator s Guide 53 1002745 02 ...
Page 132: ...132 Fabric OS Administrator s Guide 53 1002745 02 Frame Redirection 4 ...
Page 194: ...194 Fabric OS Administrator s Guide 53 1002745 02 Ports and applications used by switches 6 ...
Page 254: ...254 Fabric OS Administrator s Guide 53 1002745 02 Brocade configuration form 8 ...
Page 274: ...274 Fabric OS Administrator s Guide 53 1002745 02 Validating a firmware download 9 ...
Page 302: ...302 Fabric OS Administrator s Guide 53 1002745 02 Creating a logical fabric using XISLs 10 ...
Page 344: ...344 Fabric OS Administrator s Guide 53 1002745 02 Concurrent zone transactions 11 ...
Page 374: ...374 Fabric OS Administrator s Guide 53 1002745 02 Setting up TI over FCR sample procedure 12 ...
Page 462: ...462 Fabric OS Administrator s Guide 53 1002745 02 ...
Page 490: ...490 Fabric OS Administrator s Guide 53 1002745 02 Ports on Demand 18 ...
Page 498: ...498 Fabric OS Administrator s Guide 53 1002745 02 Supported topologies for ICL connections 19 ...
Page 626: ...626 Fabric OS Administrator s Guide 53 1002745 02 Preparing a switch for FIPS B ...
Page 630: ...630 Fabric OS Administrator s Guide 53 1002745 02 Hexadecimal Conversion C ...
Page 666: ...666 Fabric OS Administrator s Guide 53 1002745 02 ...