Instruction Manual

HITACHI Inverter

L300P Series - ... HFE

Three phase input 200/400V class

NB601EX

Summary of Contents for L300P-1100H

Page 1: ...Hitachi Europe GmbH Instruction Manual HITACHI Inverter L300P Series HFE Three phase input 200 400V class NB601EX ...

Page 2: ...sult in serious injury or death CAUTION CAUTION Indicates a potentially hazardous situation which if not avoided can result in minor to moderate injury or serious damage of product The matters described under may if not avoided lead to serious results depending on the situation Important matters are described in CAUTION as well as WARNING so be sure to observe them NOTE NOTE Notes indicate an area...

Page 3: ...rly understood before working on L300P series equipment Proper grounds disconnecting devices and other safety devices and their location are the responsibility of the user and are not provided by Hitachi Ltd Be sure to connect a motor thermal switch or overload devices to the L300P series controller to assure that inverter will shut down in the event of an overload or an overheated motor DANGEROUS...

Page 4: ... be less than 3 kHz to satisfy EMC requirements c Separate the main circuit from the signal process circuit wiring d In case of remote operating with connector cable the inverter does not conform to EMC 4 Environmental conditions when using a filter follow these guidelines a Ambient air temperature 10 40 ºC b Humidity 20 to 90 RH non condensing c Vibration 5 9 m sec 2 0 6 G 10 55Hz L300P 110 300LF...

Page 5: ...or delivering not more than 10 000 rms symmetrical amperes 480 V maximum For models with suffix H 2 Tightening Torque and Wire Range 1 WARNING Tightening torque and wire range for field wiring terminals are marked adjacent to the terminal or on the wiring diagram Model Name Tightening Torque N m Wire Range AWG L300P 110L 4 9 4 L300P 150L 4 9 2 L300P 185L 4 9 1 L300P 220L 8 8 1 0 L300P 300L 8 8 2 0...

Page 6: ...e unit shall be connected with an UL Listed inverse time circuit breaker rated 600 V with the current ratings or an UL Listed fuse as shown in the table below Model Name Tightening Torque N m Wire Range AWG L300P 110L 60 60 L300P 150L 70 70 L300P 185L 90 90 L300P 220L 100 100 L300P 300L 150 150 L300P 370L 175 175 L300P 450L 200 200 L300P 550L 250 250 L300P 750L 300 300 L300P 110H 30 30 L300P 150H ...

Page 7: ...on must be made by an UL Listed and CSA Certified closed loop terminal connector sized for the wire gauge involved Connector must be fixed using the crimp tool specified by the connector manufacturer or equivalent wording included in the manual ...

Page 8: ...Sep 1999 NB601AX 2 The data 02 of the command b004 was added The carrier frequency of the capacity 37kW and more was added Oct 1999 NB601BX 3 The specification of the capacity 75kW and more was added Jun 2000 NB601CX 4 A skipped number NB601DX 5 The specification of the capacity 90 132kW and more was added Feb 2001 NB601EX ...

Page 9: ...e weight according to the specifications in the text Chapter 6 Specifications Otherwise it may fall and there is a danger of injury p 2 1 Be sure to install the unit on a perpendicular wall which is not subject to vibration Otherwise it may fall and there is a danger of injury p 2 3 Be sure not to install and operate an inverter which is damaged or parts of which are missing Otherwise there is a d...

Page 10: ...to input a single phase Otherwise there is a danger of fire p 2 8 Be sure not to connect AC power supply to the output terminals U V W Otherwise there is a danger of injury and or fire p 2 5 Be sure not to connect the resistor to DC terminals PD P and N directly Otherwise there is a danger of fire p 2 5 Be sure to set the earth leakage breaker or the fuse s the same phase as the main power supply ...

Page 11: ...e is a danger of injury p 3 1 Be sure not to select retry mode for up and down equipment or traveling equipment because there is output free running mode in term of retry Otherwise there is a danger of injury and or machine breakage p 3 1 Even if the power supply is cut for a short period of time it may restart operation after the power supply is recovered if the operation command is given If it m...

Page 12: ...nd during the test run Otherwise there is a danger of machine breakage Was the direction of the motor correct Was the inverter tripped during acceleration or deceleration Were the rpm and frequency meter correct Were there any abnormal motor vibrations or noise p 3 2 4 Maintenance inspection and part replacement After a lapse of more than 10 minutes after turning off the input power supply perform...

Page 13: ...Terminal Connection Diagram 2 6 2 2 2 Main circuit wiring 2 8 2 2 3 Terminal Connection Diagram 2 13 2 2 4 Digital operator wiring 2 15 Chapter 3 Operation 3 1 Operation 3 3 3 2 Test Run 3 4 Chapter 4 Explanation of Function 4 1 About Digital Operator OPE SR 4 1 4 2 Code list 4 5 4 3 Explanation of function 4 10 4 3 1 Monitor mode Output frequency monitor Output current monitor Operation direction...

Page 14: ...ction function selection Electronic thermal function Overload restriction Overload advance notice Start frequency Reduced voltage start selection BRD dynamic braking function Cooling fan operating selection Intelligent input terminal setting Input terminal a b NO NC selection Multi speed operation function Jogging operation JG Second control function SET Software lock mode selection SFT Free run s...

Page 15: ...4 4 3 Warning Monitor display Chapter 5 Maintenance Inspection 5 1 Precaution for Maintenance Inspection 5 1 1 Daily inspection 5 1 2 Cleaning 5 1 3 Regular inspection 5 2 Daily inspection and regular inspection 5 3 Megger test 5 4 Withstand Voltage test 5 5 The method to check Inverter converter part 5 6 Capacitor Life Curve Chapter 6 Specification 6 1 Standard specification list 6 2 Dimension 4 ...

Page 16: ...e product is the one you ordered by checking the specification label 1 1 2 Instruction manual This instruction manual is the manual for the HITACHI Inverter L300P Series Before operation of the Inverter read the manual carefully After Reading this manual keep it to hand for future reference When using optional units for this inverter please refer to the instruction manuals packed with the optional...

Page 17: ...by unauthorized personnel 2 Any damage sustained other than from transportation Which should be reported immediately 3 Using the unit beyond the limits of the specification 4 Natural Disasters Earthquakes Lightning etc The warranty is for the inverter only any damage caused to other equipment by malfunction of the inverter is not covered by the warranty Any examination or repair after the warranty...

Page 18: ... Connector Installation point of self contained option Control circuit terminals Main circuit terminals Wiring blind cover Front cover removed Power lamp Alarm lamp Digital operator Spacer cover Terminals cover Specifications Label Front cover Note When you use cable for remote operation please remove connector ...

Page 19: ...specifications in the text Chapter 6 Specifications Otherwise it may fall and there is a danger of injury Be sure to install the unit on a perpendicular wall which is not subject to vibration Otherwise it may fall and there is a danger of injury Be sure not to install and operate an inverter which is damaged or parts of which are missing Otherwise there is a danger of injury Be sure to install it ...

Page 20: ...ut current will be reduced P 4 18 The temperature should be measured in the air gap surrounding the Inverter shown in the diagram above If the temperature exceeds the allowable temperature the component life will become shortened especially in the case of the Capacitors 4 Operating Environment Humidity The humidity surrounding the Inverter should be within the limit of the allowable percentage ran...

Page 21: ...re around is within the limit of the allowable range 8 External cooling of Inverter It is possible to install the inverter so that the heatsink is out of the back of the enclosure This method has two advantages cooling of the inverter is greatly increased and the size of the enclosure will be smaller To install it with the heatsink out of the enclosure a metal fitting option is required to ensure ...

Page 22: ...er bushes with nippers or cutters 2 Cable entry through Conduit After taking out the rubber bushes connect the conduit Note Except for when connecting conduit Do not take out the rubber bushes It is possible that the wiring insulation is broken and a possible earth fault is caused Chapter 2 Installation and Wiring Rubber bushes Wiring cover ...

Page 23: ...ase Otherwise there is a danger of fire Be sure not to connect AC power supply to the output terminals U V W Otherwise there is a danger of injury and or fire Be sure not to connect the resistor to DC terminals PD P and N directly Otherwise there is a danger of fire Be sure to set the earth leakage breaker or the fuse s the same phase as the main power supply in the operation circuit Otherwise the...

Page 24: ...ligent output 2 connection R S T R0 T0 U V W P PD RB N IM PLC P24 FW 4 3 1 5 FM CM1 TH H O O2 OI L AM AMI DC24V SP SN RP SN Option 1 Option 2 For terminal resistance RS485 Put and take as terminal substrate AL0 AL1 AL2 Braking resistor Option Shortbar Short bar at sink type Forward Thermistor 0 10V 8 bit DC0 10V 12bit DC4 20mA 12bit DC 10 0 10V 12 bit 200 240V 10 50 60Hz 5 380 480V 10 50 60Hz 5 1 ...

Page 25: ... PD RB N IM P LC C M1 P 24 FW 4 3 1 5 FM CM1 TH H O O2 OI L AM AMI DC24V SP SN RP SN Option 1 Option 2 For terminal resistance RS485 Put and take as terminal substrate AL0 AL1 AL2 Braking resistor Option Shortbar Short bar Forward Thermistor 0 10V 8bit DC0 10V 12bit DC4 20mA 12bit DC 10 0 10V 12bit 200 240V 10 50 60Hz 5 380 480V 10 50 60Hz 5 1 2 HITACHI POWER ALARM Hz V A kW MIN MAX RUN PRG RUN FU...

Page 26: ... and electric thermal rate Allowable output less than Impedance 250 ohm FM Digital monitor voltage Output the output frequency with digital besides above monitor Allowable maximum current 1 2mA Maximum frequency 3 6kHz P24 Interface power It is DC24V power for connection input signal When selecting source logic it s for connection input common Allowable maximum output current 100mA CM1 Interface p...

Page 27: ...maged in the case shown below Be careful When an unbalance of the power supply voltage is more than 3 Power supply capacity 10 times of the capacity of inverter and a case beyond 500kVA When a change in the rapid power supply voltage occur Example When inverter of the plural is installed with the common electric wire whose it is short by each other When there is insertion of the condenser or a rem...

Page 28: ...drawn through the BRD 5 Regenerative breaking unit connection terminals P N The Inverters rated more than 18 5kW don t contain a BRD circuit If regenerative braking is required an external BRD circuit Option is required along with the resistor Option Connect external regenerative braking unit terminals P N to terminals P N on the inverter The braking resistor is then wired into the External Brakin...

Page 29: ...M8 L300P 220 300LF R0 T0 M4 Earth terminal M6 Other M8 L300P 450 550LF R0 T0 M4 Earth terminal M6 Other M10 L300P 750LF L300P 900 1320HF R0 T0 M4 Earth terminal M8 Other M10 Chapter 2 Installation and Wiring W T3 R L1 PD 1 S L2 T L3 U T1 V T2 P N RB G G R0 T0 Charge lamp Short bar R L1 S L2 T L3 PD 1 P N U T1 V T2 W T3 G G Short bar R0 T0 Charge lamp R L1 S L2 T L3 PD 1 P N U T1 V T2 W T3 R0 T0 Sh...

Page 30: ...on Thermal relay preventing misapplication ACL Running motors with the inverter generates vibration greater than that with commercial power supply This part installed between the inverter and motor reduces torque ripple When the cable length between the inverter and motor is long 10m or more a countermeasure for a malfunction of the thermal relay by harmonic due to switching on inverter is taken b...

Page 31: ...9 EX60B 60A 50A H50 22 L300P 220HF 14 4 14 4 10 M6 14 6 4 9 RX100 75A 50A H50 30 L300P 300HF 22 3 22 3 10 M6 22 6 4 9 RX100 100A 70A H65 37 L300P 370HF 38 1 22 3 8 M6 38 6 4 9 RX100 100A 80A H80 45 L300P 450HF 38 1 22 1 8 M8 38 8 8 8 RX225B 150A 100A H100 55 L300P 550HF 60 1 0 30 1 6 M8 60 8 8 8 RX225B 175A 125A H125 75 L300P 750HF 100 38 2 2 50 1 0 6 M8 100 8 38 8 8 8 RX225B 225A 150A H150 90 L30...

Page 32: ... output wires of the control circuit terminals Connect the screen to the common terminal 3 Limit connection wires to 20m When it is necessary to wire over 20m use a VX applied controller RCD A Remoter operation bar or a CVD E Insulated signal transducer 4 Separate the control circuit wiring from the main power and relay control wiring 5 If control and power wires must cross make sure they cross at...

Page 33: ...etween PLC and CM1 4 The connection to the input programmable logic controller sequencer To use interface power within inverter To use outside power Take off the short bar of control terminal Chapter 2 Installation and Wiring Source type DC24V Inverter YTS48 type Output module S COM P24 PLC CM1 FW 5 Short bar DC24V DC24V COM S P24 PLC CM1 Inverter YTS48 type Output module FW 5 The terminal screw s...

Page 34: ...emote operating put off digital operator from inverter and use connector cable ICS 1 1m or ICS 3 3m Note 1 When using connector cable be sure to use less than 3m length Otherwise there is a danger of malfunction Note 2 In case of remote operating with connector cable the inverter does not conform to EMC Chapter 2 Installation and Wiring ...

Page 35: ...select retry mode for up and down equipment or traveling equipment because there is output free running mode in term of retry Otherwise there is a danger of injury and or machine breakage Even if the power supply is cut for a short period of time it may restart operation after the power supply is recovered if the operation command is given If it may incur danger to personnel be sure to make a circ...

Page 36: ...f a motor is operated at a frequency higher than standard setting value 50Hz 60Hz be sure to check the speeds of the motor and the machine with each manufacturer and after getting their consent operate them Otherwise there is a danger of machine breakage Check the following before and during the test run Otherwise there is a danger of machine breakage Was the direction of the motor correct Was the...

Page 37: ...itch relay etc 2 The frequency setting signals from volume or external DC0 10V DC 10 10V 4 20mA etc 2 Operation setting and frequency setting with the digital operator This is the method for operation from the digital operator which comes equipped with the inverter as standard or the remote operator SRW keypad When the digital operator sets the operation the terminals FW RV don t need to be linked...

Page 38: ...ndication code press the key once Two figures are shown Set 01 with the key or the key press the key once to set the operation setting for terminal Indication code turns back to A002 5 Set monitor mode When monitoring the output frequency set indication code to d001 and press the key once Or when monitoring the operating direction set indication code to d003 press the key once 6 Input starting ope...

Page 39: ...e key or the key press the key once to set the frequency setting for the operator Indication code turns back to A001 4 Set operator with the operation setting selection Set A002 as indication code press the key once Two figures are shown Set 02 with the key or the key press the key once to set the operation setting for the operator Indication code turns back to A002 Chapter 3 Operation 1 2 1 2 Dir...

Page 40: ...code to d003 press the key once Indication code are forward reverse or stop 8 Press the key to start operating The green LED RUN turns on a light and the indication changes in response to the monitor mode set 9 Press the key to decelerate to a stop When the frequency turn back to 0 the green LED RUN light will switch off Make sure that the direction of the motor is correct It is in danger of injur...

Page 41: ...mmand RUN STOP is set in operator RUN key Run command to start the motor But this is only valid when operation command is from the operator Be sure that the operation command display lamp is illuminated STOP STOP RESET key This key is used to stop motor or reset an alarm Volume for frequency setting This can be used to set the output frequency But this is only valid when the frequency command part...

Page 42: ...tion code 1 Push the key Push the key 2 18 times 18 times 3 Display code No of basic setting mode Display F001 Note 1 Extension function mode Display in the order of A b C H P U Push the key 1 2 Push the key 4 Display extension function mode Display A 6 times Push the key 1 2 Push the key 6 times 6 times Return to the state of 2 5 Display monitor code No Display d001 POWER A ALARM RUN PRG V Hz kW ...

Page 43: ...ng the STR key Operation command display lamplight will switch off so that operation command is now changed to the control terminal 5 Display extension function mode Display A It is possible to shift to other extension function modes monitor modes and basic modes in this state Display A002 F U N C Push the key S T R Push the key POWER A ALARM RUN PRG V Hz kW 1 2 HITACHI MIN MAX STR RUN FUNC STOP R...

Page 44: ...029 Note When you input code No there isn t in the code list A of left end blinks again Confirm code No and input it again 6 Finish setting function code No Push the Key STR Decide 9 Push the key 2 times 1 Push the key STR Confirm A Push the or key 2 times 2 1 9 times Display A029 Push the key STR RUN PRG A ALARM V Hz kW H I T A C H I FUNC STOP RESET MAX MIN STR RUN 1 2 POW ER A ALARM V Hz kW H I ...

Page 45: ...current A voltage V RUN time h power ON time h 4 13 d083 Trip monitor 3 Trip Code frequency Hz current A voltage V RUN time h power ON time h 4 13 d084 Trip monitor 4 Trip Code frequency Hz current A voltage V RUN time h power ON time h 4 13 d085 Trip monitor 5 Trip Code frequency Hz current A voltage V RUN time h power ON time h 4 13 d086 Trip monitor 6 Trip Code frequency Hz current A voltage V ...

Page 46: ...9 Multi speed9 0 00 starting frequency maximum frequency Hz 0 00 9 9 4 43 A030 Multi speed10 0 00 starting frequency maximum frequency Hz 0 00 9 9 4 43 A031 Multi speed11 0 00 starting frequency maximum frequency Hz 0 00 9 9 4 43 A032 Multi speed12 0 00 starting frequency maximum frequency Hz 0 00 9 9 4 43 A033 Multi speed13 0 00 starting frequency maximum frequency Hz 0 00 9 9 4 43 A034 Multi spe...

Page 47: ... 0 00 99 99 100 0 400 0 Hz 0 00 4 32 A097 Acceleration pattern selection 00 straight line 01 S curve 02 U curve 03 reverse U curve 00 4 33 A098 Deceleration pattern selection 00 straight line 01 S curve 02 U curve 03 reverse U curve 00 4 33 A101 OI start 0 00 99 99 100 0 400 0 Hz 0 00 9 4 20 A102 OI end 0 00 99 99 100 0 400 0 Hz 0 00 9 4 20 A103 OI start rate 0 100 20 9 4 20 A104 OI end rate 0 100...

Page 48: ...re keep 22 F R 3wire forward reverse 23 PID PID selection valid invalid 24 PIDC PID integrating reset 27 UP Remote control UP function 28 DWN Remote control DOWN function 29 UDC Remote control data clear 31 OPE Force operate ope 32 SF1 Multi speed bit1 33 SF2 Multi speed bit2 34 SF3 Multi speed bit3 35 SF4 Multi speed bit4 36 SF5 Multi speed bit5 37 SF6 Multi speed bit6 38 SF7 Multi speed bit7 39 ...

Page 49: ...mperature coefficient enable 02 NTC enable 00 9 4 57 b099 Thermistor error level 0 9999 ohm 3000 9 4 57 C061 Thermal warning level 0 100 80 9 4 36 C091 Debug mode selection 00 No display 01 Display 00 9 C101 UP DWN selection 00 No frequency data 01 Keep frequency data 00 9 4 49 C102 Reset selection 00 Trip cancel during ON 01 Trip cancel during OFF 02 Valid only during trip Cancel during ON 00 9 9...

Page 50: ...lays the direction that the Inverter output is rotating Forward reverse or stop On operating the inverter in case of forward or reverse the RUN lamp will illuminate Display F Forward o Stop r Reverse PID feedback monitor When you select PID function 01 in A071 the inverter displays the feedback value changed by A075 PID scale Display of monitor part Feedback quantity x PID scale Frequency command ...

Page 51: ...l monitor the state of the intelligent outputs Example Output intelligent terminal 12 11 ON Output alarm AL OFF Chapter 4 Explanation of function d005 Intelligent input monitor Relation code Display Black Lights up White Lights out Input intelligent terminal d006 Intelligent output monitor Relation code OFF AL 12 11 ON OFF ON Output intelligent terminal Display Black Lights up White Lights out ON ...

Page 52: ...5 00 as 50 x 1 1 55 00 Note Output frequency of FM terminal becomes same as d007 at the time of setting up the digital output frequency to the FM terminal Output voltage monitor This inverter displays the output voltage of the inverter converted into the alternating Voltage The monitor lamp V should illuminate while the contents of d013 are displayed Display 0 0 600 0 Display is in 0 1V unit Input...

Page 53: ...etails of the last trip Display contents 1 Trip Code Display anything from E01 to E79 Note 1 2 Output frequency on tripping Hz 3 Output current on tripping A 4 The direct voltage between P and N on tripping V 5 The accumulated time inverter was operating until tripping h 6 The accumulated time inverter was run until tripping h Note 1 Please refer to the pages 4 4 Protection function list 2 Trip mo...

Page 54: ...tion of the motor can be restricted Function code Data Contents 00 Forward reverse is effective 01 Only forward b035 02 Only reverse Frequency command selection Select the method of frequency command When 0 10Vdc is inputted to the frequency command by 02 L terminal operation direction of motor reverses On output frequency monitor d001 you can t get information about forward reverse So be sure wit...

Page 55: ...s Terminal select the stop after slowing down according to slowing down time or the free run stop When the second cycle is started while in free run stop the inverter follows the free run stop selection b088 and restarts Refer to the item of free run stop Set item Function code Data Contents 00 Normal stop Decelerated stop Selection on Stop b091 01 Free run stop 00 0Hz start Selection of free run ...

Page 56: ...short you set the adjustable time the adjustable time of the actual motor can t be shorter than the shortest adjustable time determined by the inertial Effect J of the mechanical system and motor torque If you set the time shorter than the shortest adjustable time a protection trip of OC or OV may occur Acceleration time ts ts Deceleration time tB tB Chapter4 Explanation of function F002 F202 1st ...

Page 57: ...must be set to 08 SET and switched on Set item Function code Setting limit Contents Base frequency A003 A203 30 1st 2nd maximum frequency Unit Hz 200 215 220 230 240 Unit V When inverter is 200V class selection is possible Motor voltage selection A082 380 400 415 440 460 480 Unit V When inverter is 400V class selection is possible 2 AVR function Even if the incoming voltage changes this function w...

Page 58: ...ced Voltage class 200V class 400V class Contents kW Maximum carrier frequency kHz Derating on carrier frequency 12kHz Maximum carrier frequency kHz Derating on carrier frequency 12kHz 8kHz 90kW to 132kW 11 12 100 12 100 15 12 100 12 100 18 5 10 90 12 100 22 4 80 12 100 30 3 70 8 90 37 8 80 10 80 45 10 95 10 95 55 6 75 10 95 75 3 70 5 60 90 6 95 110 6 85 132 6 85 Be sure to keep the above mentioned...

Page 59: ...with the intelligent input AT terminal In the case that reverse and FW forward terminals are ON the inverter operates reversely when main frequency command auxiliarly frequency command 0 A006 A005 AT terminal Main frequency command ExIstence of Auxiliarly frequency command 02 L Existence Of Reverse OFF O L No 00 ON OI L No OFF O L No No 00 01 ON O2 L No Yes OFF O L Yes 00 Example 1 ON OI L Yes OFF...

Page 60: ...2 A015 A105 01 2 Start End of O2 L terminal Set item Function code Data Contents Notes O2 start A111 400 400 Unit Hz Set starting frequency O2 end A112 400 400 Unit Hz Set ending frequency O2 start rate A113 100 100 Unit Set starting rate for external frequency command 10 10V Note 1 O2 end rate A114 100 100 Unit Set ending rate for external frequency command 10 10V Note 1 Example 3 Note 1 The rate...

Page 61: ...r value The limit of setting is about 2ms 60ms set value 1 30 Function code Limit to set Contents A016 1 30 Can set with the 1 unit Output voltage gain Regarding the voltage selected on A082 motor voltage selection as 100 set the rate of the voltage which the inverter outputs for the voltage selected Function code Limit to set Contents A045 20 100 Unit Chapter4 Explanation of function A016 O OI O2...

Page 62: ...w speeds it can cause improvement of efficiency low noise and low vibration because of lowering the output voltage V f characteristic is as follows Period The limit from 0 to 10 of base frequency is the constant characteristic Example If the base frequency is 60Hz the limit from 0 to 6Hz is constant characteristic Period The limit from 10 of base frequency to base frequency is reduced torque chara...

Page 63: ...requency7 Free V f frequency5 b108 0 Free V f frequency6 Free V f frequency4 b106 0 Free V f frequency5 Free V f frequency3 b104 0 Free V f frequency4 Free V f frequency2 b102 0 Free V f frequency3 Free V f frequency1 b100 0 Free V f frequency2 Unit Hz Free V f voltage7 b113 Free V f voltage6 b111 Free V f voltage5 b109 Free V f voltage4 b107 Free V f voltage3 b105 Free V f voltage2 b103 Free V f ...

Page 64: ...anual torque boost it should be noted that overuse will cause saturation of the motor and may cause damage The manual torque boost break point is the frequency at which the voltage torque boost is switched off and normal operation resumes To change from A041and A042 to A241and A242 an intelligent input needs to be set to 08 SET and switched on 2 Automatic torque boost The output voltage is adjuste...

Page 65: ... late time has elapsed 00 Edge movement Example 1 6 a DC braking edge level selection A056 01 Level movement Example 1 6 b Starting DC braking time A058 0 0 60 0 Unit second It is valid for inside DC braking When operating command is ON DC current is started 0 5 12 Unit kHz 11 to 75kW DC braking carrier Frequency A059 0 5 8 Unit kHz 90 to 132kW 1 DC braking carrier frequency It is possible to alte...

Page 66: ...tarted Please set DC braking time A055 or DC braking time by DB terminal paying attention to the heat of the motor Please set each setting in accordance with the system after level action or edge action are selected with A056 a Edge operation A056 00 b Level operation A056 01 Example 1 a Example 1 b Example 2 a Example 2 b Example 3 a Example 3 b Chapter4 Explanation of function FW DB Output frequ...

Page 67: ...55 DC braking action time operate DC braking according to set time After turning operating command FW OFF when output frequency reachs the set value of A052 during setting A055 DC braking is run Even if operation command is turned ON during setting time of A055 DC braking is run Example 5 a Example 6 a Level action Give priority to operaing command ignore DC braking time A055 and move to normal op...

Page 68: ... use O2 L case When using the minimum frequency limiter and 0v is inputted into O2 terminal A062 applies to both forward and reverse directions a When operation command is control terminal Terminal A002 01 Terminal Revolution when O2 is 0V FW ON A062 on forward side RV ON A062 on reverse side b When operation command is operator A002 02 F004 Revolution when O2 is 0V 00 A062 on forward side 01 A062...

Page 69: ... to jump is fj 2 Hz Acceleration stop function When the inertial moment of a load is high this is the function to wait until the slip of the motor on starting becomes smaller Use when the overcurrent trip occurs on starting Set item Function code Data Contents Acceleration stop frequency A069 0 00 400 0 Unit Hz Set the frequency to be held Acceleration stop time A070 0 0 60 0 Unit second Set the t...

Page 70: ...nents of PID 1 P action This is the action that the manipulated variable is in proportion to the command 2 I action This is the action that the manipulated variable increases with time in a straight line 3 D action This is the action that the manipulated variable is in proportion to the changing rate of command A001 Frequency command selection A005 AT selection A006 O2 selection A071 PID selection...

Page 71: ... PID Feedback signal of PID can be monitored The monitor value can be displayed by the product of PID scale A075 Monitor display Feedback x A075 setting 7 PID integral reset This is the function to clear integral value of PID action Assign 24 PIDC to intelligent input terminal It is cleared whenever PIDC is turned ON Don t turn absolutely ON PID terminal during PID action because there is a possib...

Page 72: ...eration frequency A095 A295 0 00 400 0 Unit Hz It is valid when two stage acceleration and deceleration selection A094 A294 is 01 Example 2 Two stage deceleration frequency A096 A296 0 00 400 0 Unit Hz It is valid when two stage acceleration and deceleration selection A094 A294 is 01 Example 2 Example 1 In to set A094 A294 to 00 case Example 2 In to set A094 A294 to 01 case Chapter 4 Explanation o...

Page 73: ...ough sketch reference and please decide the swelling degree There is the range which the midway adjustable speed time becomes fast in the S character pattern Time Output frequency Output frequency Time Time Output frequency Time Output frequency Time Output frequency Hz Goal frequency 100 96 9 82 4 17 6 3 1 Acceleration time to output frequency set value 100 25 50 75 10 02 10 02 Time Output freque...

Page 74: ...1 Valid Trip is cause and alarm is output Instantaneous power failure under voltage trip during stop Note 2 b004 02 Invalid Trip isn t caused and alarm isn t output during stop and deceleration by stop command 00 Restart to 16 times on instantaneous stop under voltage Instantaneous power failure under voltage retry time selection b005 01 Restart freely on instantaneous stop under voltage Frequency...

Page 75: ... OFF ON OFF inverter stand still example 6 b004 01 power supply running command inverter output AL IP ON OFF ON OFF ON OFF ON OFF inverter stand still example 7 b004 02 power supply running command inverter output AL IP ON OFF ON OFF ON OFF ON OFF inverter stand still example 8 b004 00 power supply running command inverter output AL IP ON OFF ON OFF ON OFF ON OFF inverter stand still example 9 b00...

Page 76: ...scription b012 b212 Rated Current x 0 2 to Rated Current x 1 2 Units A Example L300P 110LFU Motor current 44A Setting range 8 8 to 52 8A When electronic thermal level b012 44A time limit characteristic is right diagram 2 Electronic thermal characteristic Frequency characteristic is added up to set value of b012 Function code Deta Electronic thermal characteristic 00 Reduced torque characteristic 0...

Page 77: ...o 999 9 disable Units A Reduced rated ratio Inverter output Frequency Hz X1 0 0 60 X0 9 X0 8 5 2 5 Reduced time ratio Inverter output Frequency Hz X1 0 5 20 60 X0 8 X0 6 0 Motor current A Ratio for inverter rated current Example b012 44 A when output frequency 20Hz Trip time S 60 0 5 40 8 92 8 42 2 96 52 8 120 0 Example b012 44 A when output frequency 2 5Hz Trip time S Motor current A Ratio for in...

Page 78: ...function operates the acceleration time is longer than setting time If the overload restriction constant is set too short in spite of accelerating an over voltage trip is caused with regenerative enegy from the motor on automatic deceleration by this function When this function operates in the midst of accelerating the frequency will not reach the goal frequency the Inverter will adjust in the fol...

Page 79: ...nstant speed this is valid Overload advance notice signal output mode selection C040 01 On constant speed only this is valid 0 0 Overload advance notice is non effective Overload advance notice level C041 0 1 to Rated current x 2 0 Units A As load reaches overload advance notice level OL signal is output Overload advance notice level C040 Output current OL Inverter output frequency Overload restri...

Page 80: ...e start selection This function is to raise the voltage slowly on motor starting The lower this value the more torque is available on starting However by making this value lower the inverter has a tendency of tripping on over current protection because of almost direct starting Function code Data Time to take for reduced voltage starting 00 No reduced voltage start b036 01 06 Short about 6ms Long ...

Page 81: ...invalid BRD doesn t operate Selection of BRD b095 02 During run stop valid BRD operates Note 1 330 380 Units V In case of 200V class inverter setting is valid BRD ON Level b096 Note 1 660 760 Units V In case of 400V class inverter setting is valid Note 1 BRD ON level is the voltage setting of the DC direct current voltage of the inverter Cooling fan operating selection You can select whether the f...

Page 82: ...trol terminal Software lock 4 45 16 AT analog input voltage current select Analog external input 4 19 18 RS Reset inverter Reset inverter 4 48 20 STA 3 wire start 21 STP 3 wire stop 22 F R 3 wire direction 3 wire input function 4 50 23 PID PID selection valid invalid 24 PIDC PID integrating reset PID function 4 30 27 UP Remote control UP function 28 DWN Remote control DOWN function 29 UDC Remote c...

Page 83: ...OFF 11 speed ON OFF ON ON 12 speed ON ON OFF OFF 13 speed ON ON OFF ON 14 speed ON ON ON OFF 15 speed ON ON ON ON 2 Bit operation It is possible to set multi speed 0 to 5 by assigning 32 to 38 SF1 SF7 to the intelligent input terminals Set frequency SF1 SF7 to A021 A027 Multi speed SF7 SF6 SF5 SF4 SF3 SF2 SF1 0 speed OFF OFF OFF OFF OFF OFF OFF 1 speed ON 2 speed ON OFF 3 speed ON OFF OFF 4 speed ...

Page 84: ...op on jogging stop A039 Note 2 05 Direct braking on jogging stop Valid Example 2 Note 1 Note 1 When using the jogging function turn FW terminal or RV terminal ON after the JG terminal is turned ON It is the same when the operation command point is from the operator Note 2 In the case that the setting of A039 is 02 or 05 data setting of DB is necessary When DB data is not setting the inverter opera...

Page 85: ...eceleration frequency b012 b212 1st 2nd electronic thermal level b013 b213 1st 2nd electronic thermal characteristic selection H003 H203 1st 2nd allowable motor selection H004 H204 1st 2nd allowable motor pole selection H006 H206 1st 2nd stabilized constant Display during setting isn t differentiated between the 1st control function or the 2nd control function So confirm it in the state of ON OFF ...

Page 86: ... valid for selection b091 on stopping Set item Function code Data Description 00 0Hz start Example 1 Free run stop Selection b088 01 Equaling frequency start Example 2 Retry wait time b003 0 3 100 Units second Time until restart after FRS terminal is OFF This is also used for Instantaneous restart Frequency setting to match b007 0 00 400 0 Units Hz instantaneous stop reference to item of insuffici...

Page 87: ...arth Leakage Breaker ELB trips on ground fault the commercial circuit will not operate When a backup is required take the supply from the commercial circuit ELBC For FWY RVY CSY use control relays The sequence above is reference to the circuit and timing diagram below If an over current trip occurs when frequency matching extend the retry wait time b003 When the power is supplied to the inverter a...

Page 88: ...set time until restart is tried Frequency setting to match b007 0 00 400 0 Units Hz Reference to items of instantaneous stop under voltage 00 On ON signal trip cancel Example 1 On normal this is valid output cuts off 01 On OFF signal trip cancel Example 2 On normal valid output cuts off Reset selection C102 02 On ON signal trip cancel Example 1 On normal this is invalid only trip cancel 00 0Hz sta...

Page 89: ...nction will not operate when the external analog frequency command or the jogging operation is used Acceleration time operates according to F002 F003 F202 F203 when UP DWN terminal is ON To change 1st 2nd control assign 08 SET to an intelligent input terminal change with SET terminal It is possible for the Inverter to retain the frequency setting value from the UP DWN terminals Parameter C101 swit...

Page 90: ...ommand selection A002 to control terminal 01 Assign 20 STA 21 STP and 22 F R to three of the intelligent input terminals and the operation becomes possible as follows When the terminal is assigned STP terminal FW terminal and also RV terminal become invalid If all three inputs are not assigned this function will not operate The FW terminal and RV terminal become redundant when the 3 wire control i...

Page 91: ...gnal at the time of over setting frequency Frequency arrival signal 4 53 03 OL Overload advance notice signal Overload advance notice signal 4 38 04 OD output deviation for PID control PID function 4 30 05 AL Alarm signal Protection function 06 FA3 Arrival signal for only setting frequency Frequency arrival signal 4 53 08 IP Instantaneous stop signal 09 UV Under voltage signal Instantaneous stop u...

Page 92: ... output terminal 11 or 12 terminal ON Close On OFF Open 00 a contact Off Open ON Open On OFF Close 01 b contact Off Open 2 Specification of the alarm relay output terminal The specifications of the alarm relay output terminal is a changeover contact Action is as follows Example on using as alarm State of output terminal C036 Set value Power source State of inverter AL1 AL0 AL2 AL0 On abnormal Clos...

Page 93: ...ng frequency maximum frequency Hz When OFF OFF with 2 of setting frequency maximum frequency Hz However in to set 06 FA3 case when inverter accelerate When ON 1 of setting frequency maximum frequency Hz When OFF 2 of setting frequency maximum frequency Hz When inverter decelerates When ON 1 of setting frequency maximum frequency Hz When OFF 2 of setting frequency maximum frequency Hz Set item Func...

Page 94: ... output frequency matches the arrival frequency set in C042 C043 on adjustable speed time Chapter 4 Explanation of function Setting frequency Example max frequency f max 120 Hz setting frequency f set 60 Hz f on 120 x 0 01 1 2 Hz f off 120 x 0 02 2 4 Hz On acceleration ON with 60 1 2 58 8 Hz On deceleration OFF with 60 2 4 57 6 Hz FA1 Output frequency f Off f On F on 1 of maximum frequency F off 2...

Page 95: ... the signal is off and becoming the frequency and operation command from an operator forcibly if the signal is on when the compulsion operation function is selected by an intelligent input selection When changed the operation command while driving operation command is canceled and become stoppage at first Operation command from each command input the operation command once again as the stoppage at...

Page 96: ...ge Example 1 0 100 05 Input electric power Example 1 0 200 06 Thermal load ratio Example 1 0 100 C027 07 LAD frequency Example 1 0 Max frequency Hz 2 FM adjustment This function is used to calibrate a meter connected to the FM terminal Function code Set range Description b081 0 255 Change one by one Calibration methods 1 Connect meter to FM CM1 2 Adjust b081 so that the meter is reading the same a...

Page 97: ...ustment C087 0 255 After offset adjustment with C088 adjust according to memory AMI offset adjustment C088 0 0 20 0 Units mA External thermistor TH Temperature protection of the external machine is possible by the use of a Thermistor fitted to your motor Wire the thermistor between control terminals TH and CM1 Set the following function according to the thermistor specification Set item Function c...

Page 98: ... Initializing setting for America Initialization methods After setting the above parameters initialize as follows Chapter 4 Explanation of function b084 Initialization selection b085 Initial data selection Relation code POWER A ALARM RUN PRG V Hz kW 1 2 H I T A C H I MIN MAX STR RUN STOP RESET FUNC 1 Hold down the FUNC UP and DOWN key and then press the STR key When the display starts to flash and...

Page 99: ...9 00 3 C001 C005 02 03 04 05 A028 A035 Note Multi speed function 4 A044 A244 02 b100 b113 Control methods 5 A051 01 A052 A059 DC control 6 A071 01 A072 A076 C044 PID function 7 A094 01 A095 A096 2 stage adjustable frequency 8 b013 b213 02 b015 b020 Electric thermal characteristic 9 b021 01 02 b022 b023 Overload restriction 10 b024 01 02 b025 b026 Overload restriction2 11 b095 01 02 b090 b096 BRD f...

Page 100: ...tabilized factor H006 H206 0 255 Raise or lower when hunting occurs Operation selection on option error When an add in option is the cause of a protective trip this function can be used to switch the trip facility off and allow the Inverter to carry on in it s operation Set item Function code Data Description 00 TRP inverter trip and output alarm when option error occurs Operation selection on opt...

Page 101: ... 8 bit Selection with Operator Parity No parity even odd Selection with Operator Stop bit 1 2 bit Selection with Operator Start methods One way start form by command of host side Waiting time 0 1000 ms Setting with operator Connect form 1 N N Maximum 32 Station number is selected with operator Error check Overrun Fleming BCC Vertical Horizontal parity Chapter 4 Explanation of function Control term...

Page 102: ...ines _ _ _ SP SN RP SN Set item Function code Set value Description 02 Operator 03 RS485 04 Option 1 Data command C070 05 Option 2 02 Loop back test 03 2400 bps 04 4800 bps 05 9600 bps Communicating transmission speed C071 06 19200 bps Communication code C072 1 to32 This assigns the station number of the inverter This is used when you control more than one simultaneously 7 7 bit Communication bit ...

Page 103: ...mand description Advisability of all code Notes 00 Forward backward stop command 9 01 Setting of frequency command 9 02 Setting of intelligent terminal state 9 03 Collective reading of monitor data 04 Reading of inverter state 05 Reading of trip history 06 Reading of 1 setting item 07 Setting of 1 set item 9 08 Returning of each set value to initial value 9 This doesn t operate unless b084 is set ...

Page 104: ...ncy command Set up A001 in 03 in the case that this command is used Transmission frame Frame format Explanation Data size Value STX Control code Start of TeXt 1 byte STX 0x02 Code Station number of inverter 2 byte 01 32 and FF broadcast Command Transmission command 2 byte 01 Data Transmission data tenth ASCII code 6 byte Note 2 Reference BCC Block check code 2 byte Exclusive OR of Code Command and...

Page 105: ...R 3 wire direction 0000000000000008 CF2 multi speed2 binary operation 0000000000800000 PID PID selection valid invalid 0000000000000010 CF3 multi speed3 binary operation 0000000001000000 PIDC PID integral reset 0000000000000020 CF4 multi speed4 binary operation 0000000002000000 0000000000000040 JG jogging inching operation 0000000004000000 0000000000000080 DB external DC control 0000000008000000 U...

Page 106: ... CR 0x0D STX Code Data BCC CR Monitor item Units Compe titive rate Data size Explanation Output frequency Hz x100 8 byte Tenth ASCII code Output current A x10 8 byte Tenth ASCII code Revolution direction 8 byte 0 stop 1 forward 2 backward PID feedback monitor x100 8 byte Tenth ASCII code Intelligent input monitor 8 byte Note 5 reference Intelligent output monitor 8 byte Note 6 reference Frequency ...

Page 107: ...e Command and Data 5 Reference CR Control code Carriage Return 1 byte CR 0x0D Note 7 The data to indicate status contents of inverter is constructed from the following three factors A B C Data Inverter status A Inverter status C Inverter status B STX Code Command BCC CR STX Code Data BCC CR Code Status 00 Initial status 01 Vdc on waiting settlement 02 On stopping 03 On running 04 On FRS 05 On JG 0...

Page 108: ... byte Exclusive OR of Code Command and Data 5 Reference CR Control code Carriage Return 1 byte CR 0x0D Note 8 The monitor data trip history on trip memorizes the last six errors with an accumulated count number 8byte _ _ _ STX Code Command BCC CR STX Code Data BCC CR Accumulated count number Trip history 1 Trip history 6 Monitor item Units Magnifi cation Data size Notes Trip factor 8byte Cord disp...

Page 109: ...byte Note 10 BCC Block check code 2 byte Exclusive OR of Code Command and Data 5 Reference CR Control code Carriage Return 1 byte CR 0x0D Note 10 When data is the selected item this transmits and receives corresponding to station number On abnormal reply 4 ii reference viii 07 command This sets 1 set item Transmission frame Frame format Explanation Data size Value STX Control code Start of TeXt 1 ...

Page 110: ...EPROM or not Transmission frame Frame format Explanation Data size Value STX Control code Start of TeXt 1 byte STX 0x02 Code Station number of inverter 2 byte 01 32 Command Transmission command 2 byte 09 BCC Block check code 2 byte Exclusive OR of Code Command and Data 5 Reference CR Control code Carriage Return 1 byte CR 0x0D Transmission frame Frame format Explanation Data size Value STX Control...

Page 111: ...Reference xii 0B command This recalculates the internal motor constants This function is required when base frequency and parameter of H is changed by RS485 communication Transmission frame Frame format Explanation Data size Value STX Control code Start of TeXt 1 byte STX 0x02 Code Station number of inverter 2 byte 01 32 Command Transmission command 2 byte 0B BCC Block check code 2 byte Exclusive ...

Page 112: ...BCC CR STX Code NAK Error code BCC CR Explanation Data size Value STX Control code Start of TeXt 1 byte STX 0x02 Code Station number of inverter 2 byte 01 32 NAK Control code Negative ACKnowledge 1 byte NCK 0x06 Error code Error contents of Communication 2 byte Note 11 BCC Block check code 2 byte Exclusive OR of Code Command and Data 5 Reference CR Control code Carriage Return 1 byte CR 0x0D Error...

Page 113: ...s it as follows 3 0 3 1 3 0 3 1 3 0 3 0 3 0 3 5 3 0 3 0 Appendix ASCII code transformation table STX Code Command Data BCC CR 0x 02 0 1 0 1 0x 30 30 30 35 30 30 0 0 1 3 1 0 0 3 0 0 0 3 0 0 5 BCC number ASCII Code 0x 30 31 0 0 0 5 0 0 0x 30 31 0x 30 35 0x 0D Xor Xor Xor Xor Xor Xor Xor 0 5 Xor 3 5 Xor Constitution of the transmission Chapter 4 Explanation of function Character data ASCII code STX 0...

Page 114: ...ng with the operator of the inverter Please set up C071 Communication transmission speed selection to 02 Loop Back Test iii Shut the power supply of the inverter at first and please turn on the power supply once again The check is started iv When the check ends the display is as follows Normal Abnormal v Please push the reset button of the digital operator or copy unit And the setting of C071 is r...

Page 115: ...switched off CT CPU error When a mistaken action causes an error to the built in CPU the inverter output is switched off CPU External trip When a signal is given to the EXT intelligent input terminal the inverter output is switched off on external trip function select EXTERNAL USP error This is the error displayed when the inverter power is restored while still in the RUN mode Valid when the USP f...

Page 116: ... board SJ DG Item Contents Display of digital panel Display of remote operatorERR1 SJ DG Error Detect abnormal connection between the inverter main bady and SJ DG OP1 0 OP2 0 2 DeviceNet option board SJ DN Item Contents Display of digital panel Display of remote operatorERR1 DeviceNet communication error This error is displayed disconnection occurs when BusOff or timeout is occurred while the inve...

Page 117: ...g Figure left describes the direction of Dip switches See below Bottom 0 Upper 1 Bit increases from right to left switches Therefore figure left becomes formula below 1 2 0 2 1 2 0 2 0 2 1 2 29 Hex 41 dec NA32 NA16 NA8 NA4 NA2 NA1 5 4 3 2 1 0 NA32 NA16 NA8 NA4 NA2 NA1 1 0 MAC ID ON OFF DR1 DR0 DR ON OF DR1 DR0 DR ON OFF DR1 DR0 DR Chapter 4 Explanation of function Dip switch Rotary switch Setting ...

Page 118: ... time that the inverter has been running h 6 Accumulated time that the inverter has been powered up h Display trip factor Please refer to 4 4 1 Display the state of inverter on tripping During reset During stop During deceleration During constant speed During acceleration The state operation command is set with frequency command During start During DB During overload restriction 1 2 1 2 1 2 1 2 1 ...

Page 119: ...quency F001 Multi stage speed 0 A020 A220 096 Multi stage speed 1 15 A021 A035 Free v f frequency 1 6 b100 b102 b104 b106 b108 b110 Free v f frequency 7 b112 Free v f frequency 2 6 b102 b104 b106 b108 b110 Free v f frequency 1 b100 Free v f frequency 1 b100 Free v f frequency 3 6 b104 b106 b108 b110 Free v f frequency 2 b102 Free v f frequency 1 2 b100 b102 Free v f frequency 4 6 b106 b108 b110 Fr...

Page 120: ...sual odour present Check the input voltage to the inverter by using a meter during running 1 Is the supply voltage constant 2 Are all the phases of the supply balanced 5 1 2 Cleaning Make sure that the inverter is not dirty when operating Wipe clean with a soft cloth and synthetic detergent or ethanol Note Don t use solvents containing any of the following acetone benzene toluene alcohol etc as th...

Page 121: ...with capacity measure 1 2 No abnormality 3 Over 80 of rated capacity Capacity meter Relay 1 Is there abnormal sound in operation 2 Is there damage to the contacts 1 By hearing 2 By watching 1 2 No abnormality Main circuit Resistor 1 Is there any crack discoloration of resistance insulator 2 Confirm existance of breaking of wire 1 By watching cementing resistance Curl type resistance 2 Take out con...

Page 122: ...f R S T PD P N RB U V and W After the megger test is complete reconnect the J61 connector as before 5 4 Withstand Voltage test Never perform withstand voltage test on the inverter The inverter main circuit uses semiconductors Semiconductors can deteriorate when a withstand voltage test is performed Chapter 5 Maintenance Inspection IM R S T U V P PD N RB J61 Earth terminal Disconnect power source M...

Page 123: ...e smoothing capacitor the inverter conducts instantly and an infinite value isn t indicated Ohm number 10 ohms is indicated on conducting The values indicated will not be exactly the same for each terminal however they will be very close together If there is a significant difference a problem may exist Pole of tester Red Black Measure value R PD No conduct D1 PD R Conduct S PD No conduct D2 PD S C...

Page 124: ...erature is the temperature of the internal air of the cabinet Note 2 DC bus capacitors are recommended to be replacing every 5 years And if the inverter is used in a worse condition this recommended replacing period is reduced Chapter 5 Maintenance Inspection 10 20 30 40 1 Ambient temperature ºC 50 0 10 2 3 4 5 6 7 8 9 10 Life time year 12h day operation 24h day operation ...

Page 125: ...ntact relay 1c contact output relay selection as follows selection fromduringrunning on arrival with constant speed over setting frequency PID over deviation Output i l Intelligent monitor output terminal Analog voltage output analog current output pulse line output Display monitor Output frequency output current frequency conversion value trip history input output terminal state input electric po...

Page 126: ...nal 2 relay outputs 1a contact relay 1c contact output relay selection as follows selection fromduringrunning on arrival with constant speed over setting frequency PID over deviation Output i l Intelligent monitor Output terminal Analog voltage output analog current output pulse line output Display monitor Output frequency output current frequency conversion value trip history input output termina...

Page 127: ...6 3 Chapter 6 Specification 6 2 Dimension L300P 110 150LF HF L300P 185 300LF HF ...

Page 128: ...6 4 Chapter 6 Specification L300P 370LF HF L300P 450 550LF HF 750HF ...

Page 129: ...6 5 Chapter 6 Specification L300P 750LF L300P 900H 1100H ...

Page 130: ...6 6 Chapter 6 Specification L300P 1320HF ...