Installation
38
•
•
•
•
•
•
The ControlNet option requires standard BNC-type conectors. Both connectors should be
used. if redundancy is required.
Network Status LEDs
Module Configuration LED
5 Network Status LED A
1 Network Status LED B
3 Configuration Status LED
# Item
4 ControlNet Connector A
2 ControlNet Connector B
1
2
3
4
5
# Item
LED State Indication
Flashing Red (1 Hz) Incorrect node configuration, duplicate MAC ID etc.
Alternating Red/Green Self test of bus controller
Red Fatal event or faulty unit
Led A or B Off Channel is disabled
Alternating Red/Green Invalid link configuration
Flashing Green (1 Hz) Temporary errors (node will self correct) or node
Green Normal operation
Flashing Red (1 Hz) Media fault or no other nodes on the network
is not configured to go on-line
State Indication
Off No power
Flashing Green (1 Hz) The 4050 has not been configured or the scanner is in Idle state
Red Unrecoverable fault(s), EXCEPTION, fatal event
Flashing Red (1 Hz) Recoverable fault(s), MAC ID has been changed after initialization, etc.
Green Operating in normal condition, controlled by a scanner in Run state