SLC & PLC5 setup:
EIP:
INT (16 bit word.). (This needs special logic programming to communicate. See
WebTech question #1387 for more information.)
DeviceNet
: defaults to INT (16 bit word.)
RIO:
defaults to INT (16 bit word.)
Siemens 315 PLC:
Profibus defaults to bytes
Example #2 Mapping an Input
We next connect a remote switch for use in Tare operations, so we must map User Switch
1 (1 of 3 inputs to the HI 4050) to Tare. The assignment statement is:
•
Destination = Source
•
Tare (HO2.0) = User Switch 1 (HI0.4)
Step 1.
Select Tare on the Control
pull-down menu. A Select
button appears.
Step 2.
When you click Select, the
Control text box displays
the destination address.
Step 3.
From the Control pull-down
list in the Source Section,
select User Switch 1. A
Select button will appear.
Step 4.
Click Select to display the
Source address in the Map
text field.
Step 5.
The Mapping Assignment Statement is complete. Tare (HO2.0) = User Switch 1.