Configuration
65
•
•
•
•
•
•
NOTE
If you don’t want to change the Voltage Low and High and Current Low and High default
values, start with the Low and High Weight values for your application.
For assistance in configuring the Analog Output Card, click
HELP
at the top of the page.
Step 3.
To Configure Channel1 (Voltage Output), rapidly click in the Chan 1 V LOW
field until the entire value is highlighted (which may take a few clicks), then type
in the value for your low voltage output.
Step 4.
Follow the same procedure to enter appropriate values for the high voltage output
(V HIGH), Low Weight, and High Weight.
Step 5.
Click Set to save the parameters at any time. However if you are configuring more
than one channel, you can wait until all the channels are configured.
Step 6.
To Configure Channels 2, 3 and 4, repeat the procedures above. Remember that
Channels 2 and 4 are current (I) outputs.
NOTE
To refine a reading of say
10.02 where you want an output reading of
10, adjust the 0-10
values to get the correct output. The formula to do this is as follows:
•
(Expected Output/Actual Output) x Expected Output = New Number
•
For example: (10/10.02) x 10 = .998 x 10 = 9.98
•
Reset your input numbers to 0-9.98.
•
This formula applies to all four channels.
Step 7.
To assign the input data to the analog output channels being used, go to the
Mapping page and follow the Instructions for Mapping in Chapter 6.