126
Chapter
6
•
•
•
•
•
•
Using a Parameter Dump to Save Settings
The Parameter dump can be used as a backup of the SD card and for duplicating setups in
other 4050 controllers.
Step 1.
Click inside the parameter dump box.
Step 2.
Select ALL
Step 3.
Copy and paste the contents into a TEXT file or Notepad.
Do not use
a word
processing document file type.
Step 4.
Reverse the order to restore data to the parameter dump.
Step 5.
Click SAVE when you have copied over the existing text with the new text. to
save the parameters to the new HI 4050 instrument.
NOTE
In some instances, the calibration data cannot be transferred between 4050 controllers
using the SD card or the parameter dump method. The problem occurs when a controller
containing the old analog weigh scale card’s data tries to copy to a controller with the new
version of the Analog weigh scale card used in the HI 4050+. The differences in the cards
prohibit a direct data transfer. That non-transferral of calibration data happens for new to
old
and
old to new.
You can tell if the controller has the latest analog weigh scale card if on the front display
HI 4050+ is displayed on the main display line.