30
Chapter
4
•
•
•
•
•
•
Direct Connection:
A direct point-to-point connection between the HI-6500 and your
desktop or laptop computer using any standard Ethernet cable. See
the
Direct Connection
section below.
LAN Connection
To connect the HI 6500 series instrument to a LAN, you simply connect a standard Ethernet
cable between the instrument and the common network hub. You will then need to
determine which scheme is used on the network to assign IP addresses. Every node on the
network must have a unique IP address or conflicts will result.
Contact your Network Administrator for the IP address to use for the instrument.
The IP address can be set manually (Fixed IP), or it can be set automatically by a network
service called DHCP.
NOTE
If the DHCP service fails, the instrument will default to the Fixed IP address after a power
cycle. If the DHCP service is repaired, the instrument will revert back to using the DHCP
IP address.
If you are required to use Fixed IP addresses, refer to the section
Fixed IP Configuration
Using the Front Panel
below. For automatic IP assignment (DHCP), use the following
steps:
DHCP Configuration Using the Front Panel
DHCP works only if a DHCP server is installed on your network.
Step 1. From the Configuration menu, Use the UP or DOWN button to select the
communication menu, then select the Ethernet TCP/IP menu item.
Step 2. Select the DHCP menu item and use the ENTER key to enable/disable this
feature.
Step 3. Select the DHCP IP address menu item and verify that a correct IP address has
been assigned to the instrument by the network server. If an incorrect IP address
has been assigned contact your system administrator; or use a Fixed IP address.
Step 4. This is the IP address to use in your web browser to access the Web Interface.
From here you can jump to the section
NOTE
You cannot change the values of the DHCP IP address. The LEFT button returns the
operator to the Ethernet TCP/IP Menu.
Summary of Contents for HI 6500 Series
Page 10: ...viii Contents ...
Page 20: ...10 Chapter 2 ...
Page 72: ...62 Chapter 4 ...
Page 96: ...86 Chapter 5 Profibus DP Commands and Parameters ...
Page 97: ...Instrument Configuration 87 Serial Option Termination ...
Page 126: ...116 Chapter 5 ...
Page 156: ...146 Chapter 8 ...
Page 163: ...Troubleshooting 153 General Troubleshooting Flow Chart Index ...
Page 164: ...154 Chapter 9 A Guideline Instability Electrical and Mechanical review ...
Page 165: ...Troubleshooting 155 A1 Checking for Unstable Components in a Weighing System ...
Page 166: ...156 Chapter 9 B Guidelines for Electrical Mechanical or Configuration Issues ...
Page 167: ...Troubleshooting 157 B1 Guidelines to Verify Electrical Installation ...
Page 168: ...158 Chapter 9 B2 Guidelines to Verify Mechanical Installation ...
Page 170: ...160 Chapter 9 C Integrated Technician and Stability Test Overview ...
Page 171: ...Troubleshooting 161 E Testing for Non Return to Zero System with IT Summing Card ...
Page 173: ...Troubleshooting 163 G Calibration Errors When Performing the Calibration ...
Page 174: ...164 Chapter 9 H Mechanical Installation ...
Page 175: ...Troubleshooting 165 J Electrical Inspection ...
Page 176: ...166 Chapter 9 K Installation Check Points ...
Page 177: ...Troubleshooting 167 M Weight Processor s Front Display is Blank or Locked ...
Page 178: ...168 Chapter 9 N Analog Out HI 6510 Only ...
Page 194: ...184 Appendix A Figure D1 Assembling the Swivel Mount Enclosure on the instrument pedestal ...
Page 196: ...186 Appendix A Dimensions ...
Page 200: ...4 HI 6500 Series USER GUIDE Index ...
Page 201: ......