9 Measurement
9.2 Measurement settings
FLUXUS G831ST-HT
2021-06-01, UMFLUXUS_G831ST-HTV1-0EN
88
Output function test
The function of the output can now be tested.
• Connect an external measuring instrument to the terminals of the installed output.
• Select
Yes
to test the output. Select
No
to display the next menu item.
• Press ENTER.
• Enter a test value. It has to be within the output range.
• Press ENTER.
If the external measuring instrument displays the entered value, the output functions correctly.
• Select
Repeat
to repeat the test or
Finish
to display the next menu item.
• Press ENTER.
• Select
Yes
to test the status of the output signal. Select
No
to display the next menu item.
• Press ENTER.
• Select in the scroll list
Active
or
Passive
.
• Press ENTER.
If the external measuring instrument displays the value (min. output value for
Passive
, max output for
Active
), the
output functions correctly.
• Select
Repeat
to repeat the test,
Finish
to display the next menu item.
• Press ENTER.
Options\Outputs\...\Test signal
Options\Outputs\...\Enter test value
Options\Outputs\...\Test mea. range
Options\Outputs\...\Enter test value