XDM-300 Installation and
Maintenance Manual
Rack
Installation
417006-2311-0H3-A00 ECI
Telecom
Ltd.
Proprietary
B-5
Rack Installation on Floating (Suspended)
Floors
This section describes how to install racks on floating (suspended) floors.
To mount the rack on a floating (suspended) floor:
1.
Drill the required mounting holes in the suspended floor in accordance with
the appropriate template.
2.
Position the rack over the mounting holes.
3.
Secure the rack to the floor in accordance with diagram c. of Mounting
diagrams for ETSI racks (on page
Suspended Overhead Tray Assembly
This section describes how to install racks on a suspended overhead tray.
To mount the rack on a suspended overhead tray:
1.
Refer to the suspended overhead tray diagram (see the following figure)
and position the overhead rack securing brackets.
2.
Secure the rack to the overhead cabling trays, using the adjustable brackets.
2200 mm high racks may also be attached to the ceiling; 2600 mm racks
are generally attached only to the ceiling.
UPPER BRACKET
LOCK WASHER
LOCK WASHER
SCREW M8X20
SCREW M8X20
FLAT WASHER
FLAT WASHER
FLAT WASHER
NUT M8
NUT M8
CEILING
64
0
M
A
X
50
M
IN
550
CEILING
Figure
B-3: Rack mounting diagram for attachment to suspended overhead
tray (2200 mm rack)