Equipment Installation
XDM-300 Installation and
Maintenance Manual
3-42 ECI
Telecom
Ltd.
Proprietary
417006-2311-0H3-A00
Installing the XDM-300 Shelf in the Vertical
Position
Before installing the XDM-300 shelf (in the vertical position), in an ETSI A
rack, you must prepare it by performing the following steps:
|
Remove the horizontal installation brackets.
|
Install the lower vertical bracket.
|
Attach the vertical filter housing.
|
Install the upper vertical bracket.
|
Insert the vertical air filter.
The components required for the vertical installation are supplied in the
installation kit. The procedures required for preparing the XDM-300 for
vertical installation follow.
C
AUTION
:
When installing an XDM-300 shelf vertically,
pay attention to position the shelf with the FCU300 facing
downwards. This is important to ensure proper ventilation of
the XDM-300 shelf.
To remove the XDM-300 shelf horizontal brackets:
1.
Place the XDM-300 shelf on a flat clean surface.
2.
Remove the four screws fastening the horizontal bracket to the right side of
the shelf.
3.
Repeat step 2 for the bracket on the left side of the shelf.
N
OTE
:
The sides of the XDM-300 shelf described hereafter
refer to the product installed in the vertical position. For
example, the lower (or bottom) side of the shelf is the side
near the FCU300.