EMR-4000
IM02602009E
RS485*
Master/Slave:
Slave
Connection:
6 screw-clamping terminals RM 3.5 mm (138 MIL)
(terminating resistors internal)
The RS485 interface is realized via terminals. The communication cable has
to be shielded. The shielding has to be fixed at the screw that is marked
with the ground symbol (rear side of the device).
LWL-Module with ST connector*
Master/Slave:
Slave
Connector:
ST-Port
Compatible Fiber:
50/125 µm, 62,5/125 µm, 100/140 µm and 200 µm HCS
Wavelength
820 nm
Minimum Optical Input Power:
-24,0 dBm
Minimum Optical Output Power:
-19.8 dBm with 50/125 µm Fiber
-16,0 dBm with 62,5/125 µm Fiber
-12,5 dBm with 100/145 µm Fiber
-8,5 dBm with 200 µm HCS Fiber
Maximum Link Length:
2.7 km (depending on link attenuation)
Please note: The transmission speed of the optical interfaces is limited to 3 MBaud for Profibus.
Optical Ethernet_module with LC connector*
Connector:
LC-Port
Compatible Fiber:
50/125 µm and 62,5/125 µm
Wavelength:
1300 nm
Minimum Optical Input Power:
-30,0 dBm
Minimum Optical Output Power:
-22.5 dBm with 50/125 µm Fiber
-19,0 dBm with 62,5/125 µm Fiber
URTD-Interface*
Connector:
Versatile Link
Compatible Fiber:
1 mm
Wavelength:
660 nm
Minimum Optical Input Power:
-39,0 dBm
*availability depends on device
www.eaton.com
838