Options of the DNP
Name
Description
-.-
No assignment
Prot.FaultNo
Waveform No.
Prot.No of GridFaults
Number of grid faults: A grid fault, e.g. a short circuit, might cause several faults with trip and autoreclosing,
each fault being identified by an increased fault number. In this case, the grid fault number remains the same.
Bkr.TripCmd Cr
Counter: Total number of trips of the switchgear (breaker, load break switch…). Resettable with Total or All.
MStart.StartPerHour
StartPerHour
MStart.SPH Release
In case that the Motor is blocked by a SPH blocking, this timer needs to be expired before the blocking is
released and the next motor start is permitted. The next Motor Start will increment the SPH counter again.
MStart.ColdStartPermit
Number of cold starts remaining
MStart.OCNT
Motor Operation count since last reset. Resettable with "Sys Res Operations Cr" or "All".
MStart.RunTime
Motor Operation time since last reset. Resettable with "Sys. Res Operations Cr" or "All".
MStart.nEmrgOvr
Number of emergency overrides since last reset. Resettable with "Sys. Res Operations Cr" or "All".
MStart.TRunTime
Motor Operation (Motor run time) time since last reset. Resettable with "Sys. Res TotalCr" or "All".
MStart.TOCS
Total Motor Operation count since last reset. Resettable with "Sys. Res TotalCr" or "All".
MStart.nTRNTrips
Number of transition trips since last reset. Resettable with "Sys. Res TripCr" or "All".
MStart.nRevTrips
Number of reverse spinning trips since last reset. Resettable with "Sys. Res TripCr" or "All".
MStart.nZSWTrips
Number of zero speed switch trips since last reset. Resettable with "Sys. Res TripCr" or "All".
MStart.nISQT
Number of incomplete sequence trips since last reset. Resettable with "Sys. Res TripCr" or "All".
MStart.nSPHBlocks
Number of start per hour blocks since last reset. Resettable with "Sys. Res Operations Cr" or "All".
MStart.nTBSBlocks
Number of time between start blocks since last reset. Resettable with "Sys. Res Operations Cr" or "All".
ECr.Wh Fwd
Positive Active Power is consumed active energy
ECr.Wh Rev
Negative Active Power (Fed Energy)
ECr.VArh Lag
Positive Reactive Power is consumed Reactive Energy
ECr.VArh Lead
Negative Reactive Power (Fed Energy)
Sys.Operating hours Cr
Operating hours counter of the protective device
Sys.Hours Counter
Resettable device operation hours counter
Selectable Switchgears of the DNP
Name
Description
-.-
No assignment
Bkr.State
Signal: Breaker Position (0 = Indeterminate, 1 = OPEN, 2 = CLOSE, 3 = Disturbed)