EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
Aux Trip
Auxiliary Threshold for Temperature Trip
Only available if: Device Planning: Aux = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
Voting 1
Voting: This parameter defines how many of the selected
channels must be over its threshold level for getting a
voting trip
1 - 12
1
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 1
Winding 1
No,
Yes
Yes
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 2
Winding 2
No,
Yes
Yes
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 3
Winding 3
No,
Yes
Yes
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
WD 4
Winding 4
No,
Yes
Yes
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]