EMR-4000
IM02602009E
Switch Direction Control
Switching commands are validated before execution. When the switchgear is already in the desired position, the switch
command will not be issued again. An opened breaker cannot be opened again. This also applies for switching
command at the HMI or via SCADA.
Anti Pumping
By pressing the CLOSE command softkey only a single switching CLOSE impulse will be issued independent, how long
the softkey is actuated. The switchgear will close only once per close command.
Direct Commands of the Control
Parameter
Description
Setting range
Default
Menu path
Res Bwear Sl
Breaker
Resetting the slow breaker alarm
Inactive,
Active
Inactive
[Operation
/Reset
/Counter]
Ack TripCmd
Acknowledge Trip Command
Inactive,
Active
Inactive
[Operation
/Reset
/Flags]
www.eaton.com
410