EMR-4000
IM02602009E
51R Ground Fault Protection Signals (Output States)
Signal
Description
Active
Signal: Active
ExBlo
Signal: External Blocking
Rvs Blo
Signal: Reverse Blocking
Blo TripCmd
Signal: Trip Command blocked
ExBlo TripCmd
Signal: External Blocking of the Trip Command
Pickup
Signal: Pickup IX or IR
Trip
Signal: Trip
TripCmd
Signal: Trip Command
Active AdaptSet
Active Adaptive Parameter
DefaultSet
Signal: Default Parameter Set
AdaptSet 1
Signal: Adaptive Parameter 1
AdaptSet 2
Signal: Adaptive Parameter 2
AdaptSet 3
Signal: Adaptive Parameter 3
AdaptSet 4
Signal: Adaptive Parameter 4
51R Ground Fault Protection Counter Values
Value
Description
Default
Size
Menu path
nPickups
Number of alarms since last reset.
0
0 - 9999999999 [Operation
/History
/PickupCr]
nTripCmds
Number of trip commands since last reset.
0
0 - 9999999999 [Operation
/History
/TripCmdCr]
Commissioning: Ground Fault Protection – Non-directional [ANSI 51R]
Please test the non-directional ground overcurrent analog to the non-directional phase overcurrent protection.