Global Protection Parameters of the Zone Interlocking
In the global parameter menu for zone interlocking, two external blocking inputs (»
Ex Block1/Ex Block2«), as with other
protection modules, can be assigned to the input of the zone interlocking function so that the zone interlock function can
be blocked by an assigned function.
Via an external input signal, the zone interlocking can also be blocked if the parameter »
ExtBlockTripCMD« is assigned.
Breaker Failure Pickup flag BF.Pickup is implicitly connected to zone
interlocking, so that NO zone interlock output signal can be sent to the
upstream device if a breaker failure on downstream device is detected.
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/ZI]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/ZI]
ExBlo TripCmd
External blocking of the Trip Command of the module/the
element, if blocking is activated (allowed) within a
parameter set and if the state of the assigned signal is
true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/ZI]