EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
t-Blo-GOC
Ground Instantaneous Overcurrent Start Delay. 50X[x],
50R[x] and 50G[x] elements are blocked for the time
programmed under this parameter, while the motor is
starting
0.03 - 1.00s
0.08s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-UnderLoad
Underload Start Delay. 37[x] elements are blocked for the
time programmed under this parameter, while the motor
is starting
0 - 1200s
60s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-IUnbalance
Current Unbalance Start Delay. 46[x] elements are
blocked for the time programmed under this parameter,
while the motor is starting
0.03 - 1200.00s
10.00s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-JAM
Jam Start Delay. 50J[x] elements are blocked for the time
programmed under this parameter, while the motor is
starting
0.03 - 1200.00s
60.00s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-VUnbalance
Voltage Unbalance Start Delay. These elements are
blocked for the time programmed under this parameter,
while the motor is starting.
0 - 1200s
1s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Undervoltage
Undervoltage Start Delay. These elements are blocked
for the time programmed under this parameter, while the
motor is starting
0 - 1200s
1s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Overvoltage
Overvoltage Start Delay. These elements are blocked for
the time programmed under this parameter, while the
motor is starting
0 - 1200s
1s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-Power
Power Start Delay. These elements are blocked for the
time programmed under this parameter, while the motor
is starting
0.03 - 1200.00s
0.03s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-PowerFactor
Power Factor Start Delay. These elements are blocked
for the time programmed under this parameter, while the
motor is starting
0.03 - 1200.00s
0.03s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
www.eaton.com
470