EMR-4000
IM02602009E
These would be represented by two such vertical lines, both below the normal load current. Be sure to set the alarm
level
above
the trip level. Both trips and alarms are held off by the start delay. Each has its own run or pickup delay.
Use the start delay to block tripping until the load stabilizes after a start. Use run delays to avoid nuisance alarms or
trips for load transients.
To configure this function for operation under an alarm condition, the User must assign the functions pickup ( for
example 50J[1].Pickup) to an output relay, under >>Device Parm / Relay Outs<< that the User has identified as the
Alarm relay output. Likewise, to illuminate an LED under a functions alarm condition, LED 2 must be assigned the
functions pickup. Several elements are configure as such at the factory for convenience.
Device Planning Parameters of the Underload Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
Do not use,
Use
37[1]: Use
37[2]: Use
37[3]: Do not use
[Device Planning]
Global Protection Parameters of the Underload Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Underload-Prot
/37[1]]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Underload-Prot
/37[1]]
ExBlo TripCmd
External blocking of the Trip Command of the module/the
element, if blocking is activated (allowed) within a
parameter set and if the state of the assigned signal is
true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Underload-Prot
/37[1]]
www.eaton.com
497