EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
LB Alarm
Load Bearing Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
LB t-Delay
Load Bearing If this time is expired a Temperature Alarm
will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
LB Trip
Load Bearing Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/LB Group]
Aux Alarm Function Auxiliary Alarm Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Aux Trip Function
Auxiliary Trip Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Aux Alarm
Auxiliary Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
Aux t-Delay
Auxiliary If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux Group]
www.eaton.com
716