EMR-4000
IM02602009E
Plausibility check: In order to prevent obvious wrong settings the device
monitors constantly all temporary saved parameter changes. If the device
detects an implausibility, this is indicated by a question mark in front of the
respective parameter.
In order to make things easier to follow up, especially where complex
parameter changes are involved, on every superior/higher-ranking menu
level, above the temporary saved parameters an invalidity is indicated by
the question mark (plausibility trace). This makes it possible to control or
follow from the main menu level at any time where implausibilities are
intended to be saved.
In addition to the question mark trace to the temporary saved implausible
parameter changes a general implausibility symbol/question mark is faded-
in at the left corner of the display, and so it is possible to see from each
point of the menu tree that implausibilities have been detected by the
device.
A star/parameter change indication is always overwritten by the question
mark/implausibility symbol.
If a device detects an implausibility, it rejects saving and adopting of the
parameters.