EMR-4000
IM02602009E
Setting Group Parameters of the RTD Temperature Protection Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/General Settings]
WD 1 Alarm
Function
Winding 1 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 1 Trip Function Winding 1 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
www.eaton.com
705