EMR-4000
IM02602009E
Signal
Description
Blo-Generic2
Generic Start Delay. This value can be used to block any protective element.2
Blo-Generic3
Generic Start Delay. This value can be used to block any protective element.3
Blo-Generic4
Generic Start Delay. This value can be used to block any protective element.4
Blo-Generic5
Generic Start Delay. This value can be used to block any protective element.5
I_Transit
Signal: Current transition signal
T_Transit
Signal: Time transition signal
MotorStopBlo
Signal: Motor stop block other protection functions
RFD_IA_Normal
Signal: System IA RotaryFieldDetection Normal
RFD_IA_Reverse
Signal: System IA RotaryFieldDetection Reverse
VUnbalStartBlock
Signal: Motor start block voltage unbalance signal.
UnderVStartBlock
Signal: Undervoltage Start Delay. Undervoltage elements are blocked for the time programmed
under this parameter
OverVStartBlock
Signal: Overvoltage Start Delay. Overvoltage elements are blocked for the time programmed
under this parameter
PowerStartBlock
Signal: Power Start Delay. Power elements are blocked for the time programmed under this
parameter
PFacStartBlock
Signal: Power Factor Start Delay. Power Factor elements are blocked for the time programmed
under this parameter
FrqStartBlock
Signal: Frequency Start Delay. Frequency elements are blocked for the time programmed under
this parameter
Direct Commands of the Motor Start Module
Parameter
Description
Setting range
Default
Menu path
EmergOverHMI
Emergency override through front display
Only available if: EmgOvr = Active
Inactive,
Active
Inactive
[Operation
/Reset
/EmgOvr]
RstForcedStart
Reset Forced Start flag
Inactive,
Active
Inactive
[Operation
/Reset
/Flags]