EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
MB 1 Alarm
Function
Motor Bearing 1 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 Trip Function
Motor Bearing 1 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 Alarm
Motor Bearing 1 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 t-Delay
Motor Bearing 1 If this time is expired a Temperature
Alarm will be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 1 Trip
Motor Bearing 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 1]
MB 2 Alarm
Function
Motor Bearing 2 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 2]
MB 2 Trip Function
Motor Bearing 2 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/MB 2]
www.eaton.com
710