EMR-4000
IM02602009E
Setting Group Parameters of the 50P Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
50P[1]: Active
50P[2]: Active
50P[3]: Inactive
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
Rvs Blo Fc
Activate (allow) or inactivate (disallow) reverse blocking
of the module/element. This parameter is only effective if
a signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/element are blocked that are parameterized
"Rvs Blo Fc = active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
50P[1]: Inactive
50P[2]: Active
50P[3]: Inactive
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
Criterion
Measuring method: fundamental or rms or 3rd harmonic
(only generator protection relays)
Fundamental,
True RMS
True RMS
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
Pickup
If the pickup value is exceeded, the module/element
starts to time out to trip.
Only available if: Characteristic = DEFT Or Characteristic
= INV Minimum of the setting range If: VRestraint =
Active Minimum of the setting range If: VRestraint =
Inactive
0.02 - 40.00In
50P[1]: 2In
50P[2]: 2.5In
50P[3]: 3.0In
[Protection Para
/<1..4>
/I-Prot
/50P[1]]
www.eaton.com
505