EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
WD 5 t-Delay
Winding 5 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
WD 5 Trip
Winding 5 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 5]
WD 6 Alarm
Function
Winding 6 Alarm Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 6]
WD 6 Trip Function Winding 6 Trip Function
Inactive,
Active
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 6]
WD 6 Alarm
Winding 6 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 6]
WD 6 t-Delay
Winding 6 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 6]
WD 6 Trip
Winding 6 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 6]