EMR-4000
IM02602009E
Parameter
Description
Setting range
Default
Menu path
Trip
Signal: Zone Interlocking Trip
Inactive,
Active
Active
[Protection Para
/<1..4>
/ZI
/Zone Trip]
Fault Type
Fault Type
Phase,
Ground,
Both
Both
[Protection Para
/<1..4>
/ZI
/Zone Trip]
Zone Interlocking Output Logic [X2]
The following current protective function elements serve as the Phase Zone Interlock OUTPUT start functions:
51P[1];
50P[1]; and
50P[2].
The following current protective function serves as the Ground Zone Interlock OUTPUT start functions:
51X[1];
50X[1];
50X[2];
51R[1];
50R[1] and
50R[2].