EMR-4000
IM02602009E
Global Protection Parameters of the Motor Start Recorder
Parameter
Description
Setting range
Default
Menu path
Resolution
Resolution (recording frequency)
50ms,
100ms,
1s
50ms
[Device Para
/Recorders
/Start rec]
Motor Start Recorder Module Signals (Output States)
Signal
Description
Storing
Signal: Data are saved
Direct Commands of the Motor Start Recorder Module
Parameter
Description
Setting range
Default
Menu path
Res StartRec
Delete all start recorder records
Inactive,
Active
Inactive
[Operation
/Reset
/Flags]
Res StatisticRec
Delete all statistic recorder records (start trending)
Inactive,
Active
Inactive
[Operation
/Reset
/Flags]
Statistic Recorder
The Statistic Recorder shows motor specific statistical data on a monthly base.
The Statistic Recorder can record up to 24 monthly reports. The reports are power fail safe stored.
In order to view information from the Statistic Recorder, the User has to select [Operation/Recorder/Statisticrec] from
the menu tree.
By double clicking on the »
Date of Record«
statistics information can be viewed such as the number of starts, the
number of successful starts, the average start time, the »
average I2T«
value during any start, and the average of all
maximum currents value seen during each start.
www.eaton.com
210