Three-phase Asymmetry and Phase-sequence 
Phase-loss Relay

K8AB-PA

Ideal for 3-phase voltage asymmetry 
monitoring for industrial facilities and 
equipment.

• Monitor voltage asymmetry, phase sequence, and phase loss 

for three-phase 3-wire or 4-wire power supplies with just one 
Unit. 
Switch setting for 3-phase 3-wire or 3-phase 4-wire power 
supply.

• One SPDT output relay, 6 A at 250 VAC (resistive load).

• World-wide power specifications supported by one Unit 

(switchable).

• Relay warning status easily monitoring using LED indicator.

• Easy wiring with ferrules

×

 2.5 mm

2

 solid or 2 

×

 1.5 mm

2

 standard ferrules.

• CE mark compliance certified by third party.

UL certification pending.

Model Number Structure

Model Number Legend

1. Basic Model

K8AB: Measuring and Monitoring Relays

2. Functions

PA:

Three-phase Asymmetry and Phase-sequence Phase-loss Relay.

3. Rated Input Voltage

1:

AC 115, 127, 133, 138, 200, 220, 230, 240

2:

AC 220, 230, 240, 277, 380, 400, 415, 480

1

2 3

K8AB-

@@

Summary of Contents for K8AB-PA

Page 1: ...wire power supply One SPDT output relay 6 A at 250 VAC resistive load World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy w...

Page 2: ...Operating value setting range Asymmetry rate 2 to 22 Operating value 100 operation at set value Asymmetry operating value Rated input voltage x Asymmetry set value The asymmetry operation will functio...

Page 3: ...d exposed uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5...

Page 4: ...etry Operating Voltage Asymmetry operation condition Highest voltage Lowest voltage Asymmetry operating voltage Asymmetry operating voltage Rated input voltage V Asymmetry set value Note The rated inp...

Page 5: ...mode OFF ON 3 phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PA1 200 VAC 115 VAC OFF OFF ON OFF 22...

Page 6: ...ruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...