background image

Cat. No. N147-E1-01

Three-phase Asymmetry and Phase-sequence Phase-loss Relay

 K8AB-PA

3

Specifications

Ambient operating temperature

20 to 60°C (with no condensation or icing)

Storage temperature

40 to 70°C (with no condensation or icing)

Ambient operating humidity

25% to 85%

Storage humidity

25% to 85%

Altitude

2,000 m max. 

Voltage fluctuation range

85% to 110% of rated input voltage 

Input frequency

50/60 Hz ±5 Hz (AC power supply) 

Output relays

Resistive load

6 A at 250 VAC (cos

 φ 

= 1)

6 A at 30 VDC (L/R = 0 ms)

Inductive load

1 A at 250 VAC (cos

 φ 

= 0.4)

1 A at 30 VDC (L/R = 7 ms)

Minimum load

10 mA at 5 VDC

Maximum contact voltage

250 VAC

Maximum contact current

6 A AC

Maximum switching 
capacity

1,500 VA

Mechanical life

10,000,000 operations

Electrical life

Make: 50,000 times, Break: 30,000 times

Terminal screw tightening torque

1.2 N·m

Crimp terminals

Two solid wires of 2.5 mm

2

, two crimp terminals of 1.5 mm

2

 with insulation sleeves, can be 

tightened together

Insulation resistance

20 M

 (at 500 V) between charged terminals and exposed uncharged parts

20 M

 (at 500 V) between any charged terminals (i.e., between input, output, and power 

supply terminals)

Degree of protection

Terminal section: IP20, Rear case: IP40

Case color

Munsell 5Y8/1 (ivory) 

Case material

ABS resin (self-extinguishing resin) UL94-V0

Weight

200 g

Mounting

Mounted to DIN Track or via M4 screws

Dimensions

22.5 (W)  x 90 (H) x 100 (D) mm  

Installation environment

Overvoltage Category III, Pollution Degree 2

Application standards

EN60255-5/-6

Safety standards

EN60664-1

EMC

EMI: EN61326 Industrial applications 
Electromagnetic interference wave 

CISPR11 Group 1, Class A: CISPR16-1/-2

Terminal interference wave voltage 

CISPR11 Group 1, Class A: CISPR16-1/-2 

EMS: EN61326 Industrial applications 
Electrostatic discharge EN61000-4-2: 8 kV (in air)
Radiating radio-frequency electromagnetic field EN61000-4-3: 

10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz) 

Burst EN61000-4-4: 

1 kV (I/O signal line), 2 kV (power line)

Surge EN61000-4-5:

1 kV with line (power line), 
2 kV with ground (power line) 

Conducted RF EN61000-4-6:

3 V (0.15 to 80 MHz) 

Power frequency magnetic field immunity
EN61000-4-8: 30 A/m 
Voltage dip/short interruptions 
EN61000-4-11: 0.5 cycle, 0.180° each, polarity 100% (rated voltage) 

Summary of Contents for K8AB-PA

Page 1: ...wire power supply One SPDT output relay 6 A at 250 VAC resistive load World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy w...

Page 2: ...Operating value setting range Asymmetry rate 2 to 22 Operating value 100 operation at set value Asymmetry operating value Rated input voltage x Asymmetry set value The asymmetry operation will functio...

Page 3: ...d exposed uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5...

Page 4: ...etry Operating Voltage Asymmetry operation condition Highest voltage Lowest voltage Asymmetry operating voltage Asymmetry operating voltage Rated input voltage V Asymmetry set value Note The rated inp...

Page 5: ...mode OFF ON 3 phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PA1 200 VAC 115 VAC OFF OFF ON OFF 22...

Page 6: ...ruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: