Three-phase Asymmetry and Phase-sequence Phase-loss Relay

 

K8AB-PA

Cat. No. N147-E1-01

Ordering Information

List of Models

Note: 1.

Three-phase 3-wire or 4-wire and the input range are switched using a switch.

2.

The power supply is shared with the rated input voltage.

Ratings and Specifications

Ratings

Three-phase Asymmetry and Phase-sequence 

Phase-loss Relay

Rated input (See note 2.)

Model

3-phase 3-wire mode

AC 200, 220, 230, 240

K8AB-PA1

3-phase 4-wire mode

AC 115, 127, 133, 138

3-phase 3-wire mode

AC 380, 400, 415, 480

K8AB-PA2

3-phase 4-wire mode

AC 220, 230, 240, 277

Rated input 
voltage

K8AB-PA1

Three-phase, three-wire mode: 200, 220, 230, 240 VAC
Three-phase, four-wire mode: 115, 127, 133, 138 VAC

K8AB-PA2

Three-phase, three-wire mode: 380, 400, 415, 480 VAC
Three-phase, four-wire mode: 220, 230, 240, 277 VAC

Asymmetry 
operation 
(ASY.)

Operating value setting 
range

Asymmetry rate: 2% to 22%

Operating value

100% operation at set value
Asymmetry operating value = Rated input voltage x Asymmetry set value [%]
The asymmetry operation will function when the difference between the highest and lowest 
voltage phases equals or exceeds the asymmetry operating value. 

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating 
time (T)

Asymmetry

0.1 s to 30 s (Value when input rapidly changes from 0% to 120%.)

Phase sequence, phase loss

0.1 s max. (Value when input rapidly changes from 0% to 100%.)

Power ON lock (LOCK)

1 s or 5 s (Value when input rapidly changes from 0% to 100%. The operating time is the shortest 
at this point.)

Setting accuracy

±10% of full scale

Time error

±10% of set value (Minimum error: 50 ms)

Input frequency

45 to 65 Hz

Input impedance

100 k

 min.

Indicators

Power (PWR): Green LED, Relay output (RY): Yellow LED, Alarm outputs (ALM1/2): Red LED

Output relays

One SPDT relay (6 A at 250 VAC, resistive load) , normally closed operation (normally ON)

Summary of Contents for K8AB-PA

Page 1: ...wire power supply One SPDT output relay 6 A at 250 VAC resistive load World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy w...

Page 2: ...Operating value setting range Asymmetry rate 2 to 22 Operating value 100 operation at set value Asymmetry operating value Rated input voltage x Asymmetry set value The asymmetry operation will functio...

Page 3: ...d exposed uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5...

Page 4: ...etry Operating Voltage Asymmetry operation condition Highest voltage Lowest voltage Asymmetry operating voltage Asymmetry operating voltage Rated input voltage V Asymmetry set value Note The rated inp...

Page 5: ...mode OFF ON 3 phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PA1 200 VAC 115 VAC OFF OFF ON OFF 22...

Page 6: ...ruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: